Nabco Entrances Inc. S82 W18717 Gemini Drive,  Muskego, WI 53150 

Ph: (877) 622-2694 Fax: (888) 679-3319 Web: www.NabcoEntrances.com

 

CAUTION: All adjustments 

and final door operation must 

conform to ANSI 156.10 

Page 1 of 3 

P/N 15-13943   Rev. 8-30-12 

“Quick Set-Up” General Wiring and Settings for Acusensor 3  

For greater details, see the Acusensor 3 Manual (P.N. 15-8911-3) 

 

Acusensor Harness P/N 22-9184

DN 0343.5

 Form A relay Output, 50V 0.1A Max. (Resistance Load)

Black

 

White 

Power Supply 12 to 24V  AC / DC

Red 

Green 

Snow mode is only active when the 
temperature is at, or below 41°F (5°C) 
Level 3 has the highest immunity  

Sensors placed close to each other 
should be set to different Interference 
Prevention Settings.

 

 

Presence Timer determines the time need-
ed by the sensor to learn an area, or relearn 
changes within that area. 

Under normal circumstances the medium setting should be used. When adequate 
detection cannot be achieved, use a higher sensitivity. If the Acusensor 3 activates 
unnecessarily, use the lower sensitivity.  

Sensitivity setting

 

 

 

CAUTION: This Sensor Cannot 
be used for Presence Detection 
on the Pull Side of Swing door.

 