iVECTOR Heater/Cooler

8.0  Water Connection

Before making the pipework connections refer to section 3.0 for advice on System Design.

Connect the unit to the supply and return pipes. Pipework can
be routed from the floor or through the wall at the back of the
unit. (See options below). Connections are 3/4"bsp.

Connection directly onto the heat exchanger should be made
using straight connectors so that the pipework can more easily
be routed inside the unit.

For heating only applications the condensate collector mounted
on the chassis below the heat exchanger connections is not

needed and can be removed by unscrewing the two bracket
fixing screws. Removal of this component will aid pipework
fitting when the pipes are routed up from the floor.

For applications involving cooling, the pipework must be routed
to avoid the condensate collector. Connection to the heat
exchanger should be made using straight connectors so that 
the pipework can more easily be routed past the condensate
collector.

7.0

8.0

Pipe Routing Options

2-pipe connection

(The same options are possible for 4-pipe connection)

Note 1:

The supply pipe should be connected to the bottom

connection of the heat exchanger.

Note 2:

Isolating valves are not supplied with this unit, but

should be fitted in case of future service requirements. 
The type and size of valves and their location should be suitable
for the application. Valves should be selected in accordance with
system temperature and pressure requirements whilst taking into
account pressure drop characteristics.

Note 3: 

External pipework carrying chilled water must be

insulated. Use a suitable sealant as necessary to ensure that
condensate does not spill or leak. Once connection to the
system flow and return pipes is made, any exposed internal
pipework and isolating valves must also be insulated.

3

1

/

4

" -  4

1

/

4

"* MAX

* Dimension from chassis side to pipe centre.

25278 iVector Installation Guide US  02/01/2013  09:24  Page 8

Содержание 2-Pipe

Страница 1: ...LER 2 AND 4 PIPE MODELS INSTALLATION OPERATING MAINTENANCE AFTER SALES MANUAL JANUARY 2013 ISSUE 1 Product Serial Number Please leave this manual with the end user Part Number 1371060 25278 iVector In...

Страница 2: ...ion 10 10 0 Commissioning Procedure 14 11 0 Technical Data 15 12 0 Control System Set up and Operating Instruction 17 12 1 Unit Operation 17 12 2 Operating Modes 19 12 3 Installer s Set up Parameters...

Страница 3: ...condition of the wall itself and any additional potential forces or weights that may happen to be applied to the unit prior to finalising installation l Please leave this manual with the end user 3 0...

Страница 4: ...ode when the room temperature is significantly lower than the preset temperature Note It is also possible to electronically remove the highest fan speed from the functionality of this unit via the con...

Страница 5: ...g kit Check contents for concealed shipping damage Tools required Manual Warranty 6 23 6 4 4 1 8 5 9 16 6 15 16 1 1 2 3 18 Exploded view Grill Grill hinge Outer casing Filter Side cover Control panel...

Страница 6: ...er 7 0 Fixing 9 32 9 18 B 9 32 9 18 NOTE Do not replace outer cover until connection to system and connection to electrical supply has been completed 1 2 3 4 5 6 25278 iVector Installation Guide US 02...

Страница 7: ...hanger should be made using straight connectors so that the pipework can more easily be routed past the condensate collector 7 0 8 0 Pipe Routing Options 2 pipe connection The same options are possibl...

Страница 8: ...2 32 1 3 4 3 3 8 2 Dimensions 2 pipe h 6 COOL OUT HOT OUT HOT IN COOL IN 6 7 16 23 19 32 20 29 32 3 23 32 2 1 8 1 1 8 1 25 32 18 15 12 3 4 3 9 16 5 15 16 4 Dimensions 4 pipe 8 0 Water Connection cont...

Страница 9: ...uire provision for condensate disposal in accordance with any local regulations A drain tray is fitted for condensate collection within the unit This should be connected to a 1 2 drain pipe Alternativ...

Страница 10: ...ed electrician in accordance with current regulations l This unit is supplied with factory fitted 3 core cord 6ft in length with moulded plug For Building Management System l Connect wires from BMS an...

Страница 11: ...er to wiring diagrams below and on page 12 13 After making the electrical connections replace the side cover to the control box 3 Routing cable TRANSFORMER L N Supply 120V 60Hz FAN POWER BOARD CONTROL...

Страница 12: ...Hz 24V 60Hz 24V DC R G Y M T T M Lo Med Hi W Y G R B 2 pipe 1 valve TRANSFORMER L N Supply 120V 60Hz FAN POWER BOARD CONTROL BOARD WATER SENSOR 2 PIPE AIR SENSOR Supply 120V 60Hz 24V DC 24V 60 Hz COM...

Страница 13: ...W Y G R B HOT COLD WATER SENSOR 4 PIPE COOLING ONLY 4 pipe 2 valve TRANSFORMER L N Supply 120V 60Hz FAN POWER BOARD CONTROL BOARD WATER SENSOR 2 PIPE AIR SENSOR Input 120V 60Hz 24V 60Hz 24V DC R G Y M...

Страница 14: ...with the 2 screws l Switch on the electrical supply l Check the operation of the unit by following the operating instructions 3 l Set up the installation parameters on the controls system as necessar...

Страница 15: ...4 12055 8977 5899 4395 9141 6728 14150 10536 Performance Data 4 Pipe Relative Humidity Sensible cooling at 50 Model Flow l h 110 120 130 140 150 160 170 180 190 200 Heat Output Btu h Entering Water 65...

Страница 16: ...1 8 iV60x160 235 8 6 63 iV60x080 32 0 174 0 087 50 115 iV60x100 35 0 243 0 1215 61 140 iV60x120 44 0 314 0 6 72 164 iV60x140 53 0 383 0 73 83 189 iV60x160 65 0 454 0 227 94 215 Note 2 pipe water conte...

Страница 17: ...Factory Default Full Mode Use and keys to select operating mode Refer to section 12 2 for details Setup Parameters Refer to section 12 3 for details Select Clock Set Time Full Mode Select Comfort Sett...

Страница 18: ...l display can be accessed by pressing the and buttons for 5 seconds This action can be repeated to revert back to Easy mode 1 Heating indicator 2 Cooling indicator 3 Temperature symbol when this is di...

Страница 19: ...to one of the 9 pre set timed programs or one of the 4 user defined programs See section 12 5 for program options and setup Press OK to view the actual set temperature Comfort or Set back Night Set ba...

Страница 20: ...the BMS inputs are wrong e g P1 P2 or P3 P4 a message ERR BMS will flash and the system stops BMS control Parameter Name Default Setting Description Alternative Setting Select temperature scale dEG C...

Страница 21: ...see the other days in the program Shows the daily program Built in programs description P1 Morning Evening Weekend P2 Morning Afternoon Evening Weekend P3 Day Weekend P4 Evening Weekend P5 Morning Ev...

Страница 22: ...in the user menu then press Down for 5 seconds Use the left and right arrows to scroll through the inputs outputs from relays air sensor water sensors BMS inputs and screen to check as necessary Note...

Страница 23: ...Replacing the Filter Periodically the filter will need to be cleaned and the control system on this product will display FILT when it is time for the filter to be checked Filters can be easily removed...

Страница 24: ...hinnovation MYSON INC 49 Hercules Drive Suite 4904 Colchester VT0446 T 802 654 7500 F 802 654 7022 info mysoninc com www mysoninc com 01 01 2013 ISSUE 1 25278 iVector Installation Guide US 02 01 2013...

Отзывы: