Commercial Operation
20
Commercial Operation
The myPV CommsSafe is designed to require as little maintenance possible, but like
any equipment a little care ensures proper operation and a long life of reliable service
through the life of your Facility.
Recommended Maintenance Schedule
The myPV CommsSafe is designed to be maintenance free, and requires no regular
consumables or maintenance service under normal operational conditions.
The following table established recommended inspection frequency for preventative
maintenance scheduling.
Inspection Frequency:
Inspection
Description
Every
(Yrs)
Outage
Inspect the external and internal metal surfaces for signs of
corrosion. If corrosion is found, brush-clean affected areas to
remove oxidation and debris, prime and paint with an outdoor
rated paint specifically for metal (steel) surfaces.
1
No
Verify the UPS battery indicator lights are not red.. If any of the
UPS indicator lights are red, contact us to determine the
appropriate corrective action.
1
No
Visual
Inspection of
Cabinet (Seal,
Plastic Color,
and if there
are any
cracks)
If the plastic color changes the manufacturer has stated the
cabinets are UV rated but the dye pigment turn a bit more
yellow than when they were first installed, one thing worth
noting, long exposure to UV might cause slight discoloration
(light yellowish) that is normal and expected and not evidence
of a failure mode.
1
Содержание CommsSafe AC-1
Страница 3: ...Resources 2 Example myPV CommsSafe 2021 AC 1 Shown...
Страница 5: ...Resources 4 Back Panel for CommsSafe in Production Shown with Customer Supplied Equipment Added...
Страница 19: ...Initial Energization 18 24V DC 0 1V 23 9 24 1V voltage on the top input terminals of the UPS...
Страница 20: ...Initial Energization 19 24V DC 0 1V 6 0V 23 9 30 0V voltage on the top battery terminals of the UPS...
Страница 25: ...Troubleshooting 24 A fully seated fuse that is not blown in the AC block...