10
2 .4 .2 Diversion Charge Control DIP Switch Settings
The 8 DIP switches are located on the top of the PE terminal. Each switch is numbe-
red. The wind battery charging functions that can be adjusted with the DIP switches
follow:
DIP Switch Functions
As shown in the diagram, all the positions are in the “OFF” position except switch
number 3 and 7 which are in the “ON” position.
NOTE:
The DIP switches should be changed only when there is no power to the wind char-
ger. Turn off disconnect switches and remove all power to the wind charger before chan-
ging a DIP switch. A fault will be indicated if a switch is changed while the wind charger is
powered.
CAUTION 1:
The W4B-120C is shipped with all the switches in the “OFF” position. Each
switch position must be confirmed during installation. A wrong setting could cause damage
to the battery or other system components.
CAUTION 2:
To change a switch from OFF to ON, slide the switch up toward the top of the
wind charger. Make sure each switch is fully in the ON or OFF position.
CAUTION 3:
DIP Switch Number 1 and Number 8 are always in the OFF position.
DIP Switch Number 1 and Number 8: Always in the OFF position
DIP Switch Number 2, 3-System voltage
Switch 2
Switch 3
System Voltage
OFF
OFF
48V system
ON
OFF
24V system
OFF
ON
12V system