Technical Data
User manual 59719_hdb_en_12
24 / 65
4.3.2
Environmental characteristics
Cable length
≤30 m
Input characteristic
EN 61131-2
Type 1 + Type 3
Input filter
1 ms
Input (DI)
Output (DO)
Connection/female connector
M12
Cable cross section
≤0.75 mm²
Cable length
≤30 m
Output current
Per pin
≤2 A
Switching frequency
Resistive load
≤25 Hz
Climatic
Operating temperature
-25 °C ... +70 °C
Storage temperature
-40 °C ... +85 °C
Installation height
Above sea level
≤3000 m
Relative humidity
≤95 %
Mechanical
Vibration test
EN 60068 Parts 2-6
5 ... 500 Hz;
const. amplitude 1 mm;
acceleration 15 g
Shock test
EN 60068 Parts 2-27
50 g @ 11 ms
Electrical safety
Degree of protection
IP68
Protection class
III
Degree of pollution
2
Emitted EMC interference
Radio interference field strength
EN 61000-6-4 Emission
QP: 40 dBμ V/m
@ 30 ... 230 MHzQP: 47
dBμ V/m
@ 230 ... 1000 MHz
EMC immunity
Electrostatic
discharge (housing)
EN 61000-4-2
±4 kV @ contact
±8 kV @ air
Electromagnetic high-frequency fields
(housing)
EN 61000-4-3 RF field
10 V/m
Rapid transient electric disturbances
(burst)
DC inputs/outputs
EN 61000-4-4
±2 kV I/O supply
±1 kV data line/
±1 kV I/O line
Magnetic field
EN 61000-4-8
30 A/m @ 50 Hz
Conducted interferences,
high-frequency fields
EN 61000-4-6, asymmetric
10 V