Section 80
00-02-0829
2018-02-26
-
48 -
4.5.5 Output Feedback
WARNING:
Closed-loop proportional control is not recommended due to the non-
deterministic nature of the CAN bus.
CAN message sent by the PDM to communicate the measured values of the digital outputs channels.
Transmission Repetition
20 – 500 ms
Data Length
8 bytes
Data Page
0
PDU Format (PF)
239
Proprietary A, PDU1 format
PDU Specific (PS)
17 (11h)
DA (Source Address of the configuring display or
controller)
Priority
5
Parameter Group Number
61184 (EF00h) -
Feedback and Diagnostics
Start Position Length
Parameter Name
Reference
1
1 byte
Feedback and Diagnostics Identifier (132 or 133)
2
1 byte
Output 1 or 7 Feedback
3
1 byte
Output 2 or 8 Feedback
4
1 byte
Output 3 or 9 Feedback
5
1 byte
Output 4 or 10 Feedback
6
1 byte
Output 5 or 11 Feedback
7
1 byte
Output 6 or 12 Feedback
8
1 byte
Unused (always FFh)