Description

The ASM170 is a state of the art, automatic engine start / stop

controller with selectable warmup / cooldown, glow plug, or choke

capabilities. The ASM170 operates from a 12 or 24 volt battery and can

withstand voltage drops during cranking. It includes crank and rest

cycles, sensing circuit for crank disconnect and overspeed, overcrank,

and recrank protection on false starts. Four red LED’s indicate first out

shutdown from low oil pressure, high temperature, overcrank,

overspeed, auxiliary input, high/low level, engine stall, and no speed

signal. A fifth green LED lights when the engine has started. This same

LED flashes during the rest period while the unit is cycle cranking the

engine. A sixth LED lights when the multifunction output is operating.

This output is programmable using the DIP switches located on the

back of the unit.

The ASM170 is housed in an ABS plastic enclosure and the electronics

are encapsulated in a protective epoxy resin. Due to its low cost and

flexible features, it is ideal for generator or pumping applications.

Specifications

Power Input:

6 to 28 VDC.

Power Consumption Standby (AUTO):

<1mA.

Operating Temperature:

-40 to 185 °F (-40 to +85 °C).

Inputs:

Ground or positive inputs for high temperature, low oil

pressure, High/Low Level, Auxiliary / Remote Stop

sensors. (Note: The momentary start input must be at least 100 ms in

duration to be recognized as a valid start.)

Lamp Test:

When unit is powered up in Manual or Auto, the LED’s

light for 1 second as a test.

Outputs:

5A smart FET for cranking and multifunction output.

Sources from b.   10A smart FET for Fuel Valve (Energized to

Run) output. Sources from b.   125 ma transistor for common

failure, engine run, and auxiliary output. Sinks to battery –.

Crank Attempts:

Selectable for 3, 5, 10, or 255.

Crank / Rest Cycle Timing:

Field adjustable 1 to 30 seconds.

Multifunction Output

: Field programmable to one of the following

options: Glowplug, Cooldown, Warmup/Cooldown, Warmup, Airgate –

Overspeed Only, Airgate – Always, Choke, or Auxiliary Run output.

Shutdown Lockout Time Delay:

Field adjustable 1 to 300 seconds.

Locks out low oil pressure, high temperature, and loss of speed

shutdowns on start-up.

Crank Disconnect Speed Setting:

From 13 to 2500 Hz.

Overspeed Trip Point Setting:

From 13 to 8500 Hz.

Speed Sensing Input:

1.5VAC RMS to 140 VAC RMS.

Shipping Weight:

1 lb. (.45 kg.)

Shipping Dimensions:

6.25 x 6.25 x 4.5 in. (159 x 159 x 114 mm).

Installation Accessories

Tools for the module mounting, such as drill and screwdriver.

Optional Wire Harness Kit (40000138).

12 and 18 AWG (4.2 mm2 and 1.0 mm2) wire for hook up.

Set of wire termination tools.

Wire Termination; such as spade terminals. 1/4” crimp-on FASTON

®

receptacle.

Mounting Drill Pattern

(Do not scale or use as a template)

Mounting the ASM170 Module

1.

To mount the ASM170 module to your panel, drill six (0.25 in.

[6mm] dia.) holes for LED indicators, and two (0.203 in. [5 mm] dia.)

holes for mounting screws. See “Mounting Drill Pattern”, for

dimensions.

2.

Insert the ASM170 module from the back of the panel into the pre-

drilled holes.

3.

Secure the module in place with the two (2) screws provided.

ASM170 MURPHYMATIC

®

Micro-controller  

Installation and Operation Instructions

Please read the following information before installing

.

A visual inspection of this product for damage

from shipping is recommended before installing. It is your responsibility to have a qualified person install

this unit and make sure it conforms to local codes.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

Follow all safety warnings of the machine manufacturer.

Read and follow all installation instructions.

ASM-03024N

Revised 05-04

Section 40 and 75

(00-02-0531)

CAUTION: 

Certain danger to human and to equipment

such as applied in a mobile or marine application may occur

if some equipment is stopped without pre-warning. It is

therefore, recommended that monitored functions be limited

to alarm only or to alarm before shutdown in such applications.

0.750 in. (19 mm)

2.563 in. (65 mm)

2.750 in. (70 mm)

3.100 in. (79 mm)

1.250 in. (32 mm)

1.600 in. (41 mm)

1.950 in. (50 mm)

2.300 in. (58 mm)

2.650 in. (67 mm)

2.750 in. (70 mm)

Origin

0.260 in. (7 mm)

0.203 in. (5 mm) dia.

0.203 in.

(5 mm) 

diameter

0.900 in. (23 mm)

0.885 in.

(22 mm)

ASM-03024N page 1 of 4