5
Specifications
Description
Specification
Input Power Voltage
•
100 – 240 VAC
•
50/60 Hz
Input AC Power
0.75A (at full load (meaning Wi-Fi, internet, cell phone and 20
relays ON)
Relays
1 Amp. Up to 60% of the relays can operate at any given time.
Note:
Running relays at the above current levels provides between 50,000 – 100,000 switching
operations.
Analog Inputs
0 – 3.3 Volts
Analog Output
0 - 10 Volts; maximum load: 20 mA
Digital Inputs
3.3 Volts, 1.5 mA, dry contact
Communication
•
LAN – Standard 10/100 BaseT
•
Expansion – RS-485: 115 Kbps, 8 bit, even parity
Operating and Storage
Temperature Range
-10° to +50° C (+14° to +125° F)
Environmental Specifications
•
Altitude: -400 m to 2000 m
•
Relative Humidity: 20% - 70%
•
Main supply voltage fluctuation up to 5%
•
Overvoltage category II
Enclosure
•
Water and dust tight
•
Indoor use only
Dimensions (H/W/D)
403 x 324 x 141 mm/16 x 13 x 5.6 inches
Fuses
Fuse F2 on PS card: 3.15A, 250V
Certification
•
Disconnection device/overcurrent protection: In the building installation, use a certified 2-
pole circuit breaker rated 10A, certified in accordance with the IEC standard 60947-2 (in the
US and Canada use a Listed Brach Circuit protective circuit breaker). This step is required to
provide overcurrent protection and mains disconnection. The circuit breaker must be easily
accessible and marked as the controller disconnect device.
•
Main Supply Voltage: Permanently connect the controller to the mains in accordance with the
relevant national code. Provide fixed wiring inside a flexible conduit. Relays must be suitably
protected against overcurrent, using a circuit breaker rated at 10A.
Содержание TRIO
Страница 18: ... Munters AB 2020 18 Figure 5 Relay wiring detailed view Figure 6 Relay and port numbering ...
Страница 31: ... Munters AB 2020 31 Figure 27 Static pressure tubes NOTE After installing the RPS no Cold Start is required ...
Страница 86: ... Munters AB 2020 86 ...
Страница 88: ... Munters AB 2020 88 4 Verify that each channel is enabled ...
Страница 90: ... Munters AB 2020 90 The following screen should appear 7 15 3TESTING THE BIRD SCALE 1 Click Test ...
Страница 117: ... Munters AB 2020 117 4 Click the fan in the upper right Both fans turn blue 5 Define fans as required ...
Страница 170: ... Munters AB 2020 170 Click to view the bird scale data ...
Страница 180: ... Munters AB 2020 180 25 3 2TRIO 20 CONTAINER SPARE PARTS ...
Страница 182: ... Munters AB 2020 182 25 3 3TRIO 20 DOOR CARD SPARE PARTS ...
Страница 184: ... Munters AB 2020 184 25 3 4TRIO 20 MAIN CONTAINER SPARE PARTS ...
Страница 196: ... Munters AB 2020 196 Figure 36 Relay and port numbering 26 2 3POWER Figure 37 Power ports ...