1. Click
.
2. Define:
o
Target Offset: Adjusts all temperature curves by this amount. You can use this to
temporarily adjust all temperatures up or down for special circumstances. The offset
applies to all table parameters.
o
Sensor Low T° Below Alarm: Set value below which the “Low temperature sensor” alarm
is activated. This is a differential. Range 0.0° - 10.0°
o
Sensor High T° Above Alarm Diff: Set value above which the “High temperature sensor”
alarm is activated. This is a differential. Range 0.0° - 10.0°
o
Outside Temperature Compensation: High temperature set point = measured outside
tempe “outside temperature compensation”. Range [0.0° – 10.0°]
o
Absolute High Temperature: Set the critical temperature (maximum allowable).
10.3
Emergency Temperature Control
In the event that Trio fails to receive a signal from the temperature sensor for an extended period of time,
an alarm is triggered. Between the time that Trio stops receiving a signal and when an alarm is triggered,
ventilation remains at the current level. When an alarm is triggered:
•
If there is an outside temperature sensor,
o
ventilation is adjusted.
o
Ventilation levels will not fall lower than the Minimum Ventilation
•
If there is no outside temperature sensor
o
maintain the last known positive output (before the failure)
o
turn off negative output
o
Cooling and air quality treatment cease
Содержание Rotem Trio 20
Страница 20: ... Munters AB 2020 20 Figure 6 Relay and port numbering ...
Страница 44: ... Munters AB 2020 44 ...
Страница 99: ... Munters AB 2020 99 Refer to Tunnel Ventilation page 123 for more details ...
Страница 110: ... Munters AB 2020 110 4 Click the fan in the upper right Both fans turn blue 5 Define fans as required ...
Страница 141: ... Munters AB 2020 141 If an outside temperature sensor is enabled map timers to it if required ...
Страница 160: ... Munters AB 2020 160 23 3 2TRIO 20 CONTAINER SPARE PARTS ...
Страница 162: ... Munters AB 2020 162 23 3 3TRIO 20 DOOR CARDS SPARE PARTS ...
Страница 164: ... Munters AB 2020 164 23 3 4TRIO 20 MAIN CONTAINER SPARE PARTS ...
Страница 170: ... Munters AB 2020 170 Card Description Munters Ordering Number TUBES AND FILTERS FOR RPS NO RPS CARD 999 99 00503 ...
Страница 186: ... Munters AB 2020 186 Figure 33 Relay and port numbering 26 2 3POWER Figure 34 Power ports ...
Страница 199: ... Munters AB 2020 199 2 Insert and secure the SMA connector ...
Страница 202: ... Munters AB 2020 202 example only ...