Start Value: CO2 value at which to begin treatment
o
Stop Value: CO2 value at which to end treatment
o
Delay (Sec): Number of seconds the controller pauses before ventilating
o
Duration (Sec): Number of seconds the controller maintains the increased level of
ventilation
4. Set the CO2 Sensor Alarm (page 72).
3.4.1
CO2
T
REATMENT
H
ELP
|
S
ET
D
EFINITIONS
While viewing the CO2 Treatment menu: Press
HELP
, select SET, and press
ENTER
.
•
CO2 Treatment below Heat: Select YES or NO to enable CO2 treatment when heaters are
operating (set in
).
•
CO2 Treatment By: This parameter designates the method used when humidity or CO2
treatment begins. Normally, this parameter is relevant only when minimum ventilation is
running. When a treatment is required, select one the method to be employed:
o
Level: Increases the ventilation level when a treatment is required.
NOTE:
When employing Ventilation by Weight (refer to page 28), the controller increases the cycle
time or the level, depending on the particular settings.
o
Exhaust: Designate a specific exhaust fan (press a number key to select the fan).
o
Tunnel: Designate a specific tunnel (press a number key to select the fan).
o
None: Disables the treatment.
To enable the exhaust/tunnel options, in
Installation > Relay Outlet or Installation >
Analog Output, designate a relay/variable device as a tunnel or exhaust fan.
•
CO2 Treatment by Heaters: This parameter enables running the heaters in situations
where the CO2 level is high. Typically this can happen in cold temperatures when CO2
is produced by the heaters. By increasing the heat in the house, ventilation can then be
increased. If enabled, define:
Outside Temp Treat by Heaters: Heaters handle CO2 treatment when the outside
temperature is lower than the target temperature by this amount.
Diff to Stop Treatment by Heaters: Heaters cease the CO2 treatment if the inside
temperture is lower (or higher) than the target temperature by this amount. This
number can be positive or negative.
CO2 Treatment by Heater requires designating at least one temperature sensor as an
outside temperature sensor (refer to Temperature Definition, page Error! Bookmark not
defined.).
NOTE:
If the heaters are operating because of the interior temperature only, CO2 Treatment by
Heater is disabled.
SYSTEM PARAMETERS
CO2 TREATMENT
CO2 Treatment Below Heat
NO
CO2 Treatment By
Exh 6