Figure 30: Soft Minimum Example
11.2.2
C
ONFIGURING
S
OFT
M
INIMUM
V
ENTILATION
Configure the
1. Go to Control > Min Max Level > Set.
2. Define the following parameters:
o
Curve Points: Define the number of Min-Max levels. Range: 1 – 30. Default: 1
o
Min Max Level Control By: Set this parameter to Soft Min.
o
Soft Minimum According to: This parameter defines how the temperature curve
functions. See the
previous section
for details.
o
Cold Minimum Band (Below Heat): Minimum Cold ventilation begins when the
temperature drops by the amount of this differential below the
Range: -20.0 – 20.0 F/C. Default: 2.0
3. Go to Control > Min Max Level.