ComDry Control System
2.7 Min, max and default values
2.7.1 Humidity
This table shows the minimum, maximum and default humidity values:
Parameter
RH (%)
Dp (°C)
X (gr/kg)
Dp (°F)
X (grain/lb)
Max.
95
40
40
99
300
Default
50
9
7,3
49
51
SV_ (set
value)
Min.
5
-30
0,5
-20
2
Max.
10
10
1,0
10
10
Default
2
2
0,2
2
2
HYS_
(hysteresis)
Min.
0
0
0,0
0
0
Table 2.1 Minimum, maximum and default humidity values
2.7.2 Service time
This table shows the minimum, maximum and default service time values:
Parameter
Default setting
Max.
Min.
T— h (service time)
4000
8000
500
Table 2.2 Time, min/max and default service time values
2.7.3 Functions
This table shows the default settings and setting options of the Functions menu:
Parameter
Default setting
Options
Fan
Fan ON
Fan INT, Fan DEM
Unit
SI (metric units)
IP (imperial units)
Dp (°C / °F)
Humidity
RH (%)
X (gr/kg) / (grain/lb)
Table 2.3 Default settings and setting options of the Functions menu
MEN-CDCS-A1808
Menus and parameters
17