ComDry M160L
10.4 Technical data
Process air
(1)
Free-blowing air 50/60 Hz (m³/h)
160
Rated airflow at 40 Pa (m³/h)
150
Max. static pressure 50/60 Hz (Pa)
225
Fan motor power (kW)
0,09
Reactivation air
Heater power (kW)
0,84
Factory set reactivation temperature (Rt) limit (°C)
130
Temperature increase across heater (°C)
100
Fan motor power (kW)
0,08
Other
Drive Motor Power (W)
5
Sound pressure level, Low speed free-blowing process fan (dBA)
55
Sound pressure level, Normal speed free-blowing process fan (dBA)
61
Sound pressure level, High speed free-blowing process fan (dBA)
67
Electrical protection class (casing)
IP33
Electrical protection class (electric panel )
IP54
Fan Motor Winding Insulation Class
Class B
Drive Motor Winding Insulation Class
Class B
Rotor type
HPS
Air filter G3, article number
150-012054-001
Environmental conditions
Operating temperature (°C)
0... +30
Maximum installation altitude, above sea level (m)
2000
Transport and storage temperature (°C)
-20... +70
Total power, voltage and current
Version
Voltage (V)
115
230
Frequency (Hz)
50/60
50/60
Total power (W)
1010
1010
Current (A)
8,8
4,4
Fuse
3 AG, 250 VAC, 10 A Slow
3 AG, 250 VAC, 6 A Slow
(1)
The specified performance is based on 20 °C and air density of 1.2 kg/m³.
Table 10.2 Technical data M160L
41
Technical specification
190TEN-1098-D1404
Содержание comdry m170l
Страница 46: ......
Страница 48: ...www munters com ...