11. Troubleshooting 

Troubles and causes of air conditioner 

If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer. 

 

The operation lamp is flashing rapidly (five times  per second), you disconnect the unit with the power and 

then connect the unit with the power again after two or three minutes but the lamps still flash. 

 

Switch operations are erratic. 

 

The fuse is blown frequently or the circuit breaker is tripped frequently. 

 

Foreign matter or water has fallen inside the air conditioner. 

 

Water leaks from the indoor unit. 

If the system does not properly operate except the above mentioned cases or the above mentioned malfunctions 

are evident, investigate the system according to the following procedures. 

Symptoms 

Causes 

Solution 

Unit does not start. 

•  Power failure/ 
•  Power switch is off. 
•  Fuse of power switch may have burned. 
•  Batteries of remote controller exhausted 

or other problem of controller. 

•  Wait for the comeback of 

power. 

•  Switch on the power. 
•  Replace the fuse. 
•  Replace the batteries or check 

the controller. 

Air flowing normally but 
completely can’t cooling. 

•  Temperature is not set correctly. 

•  Set the temperature properly. 

Units start or stop frequently. 

•  Air or no concreting gas in the watering 

circuit. 

•  Three-way valve is malfunction. 
•  Voltage is too high or too low. 
•  System circuit is blocked. 
•  Temperature is not set correctly. 

•  Vacuum. 
•  Maintenance or change 

three-way valve. 

•  Install manostat. 
•  Find reasons and solution. 

Low cooling effect. 

•  Indoor unit heat exchanger is dirty. 
•  The air filter is dirty. 
•  Inlet/outlet od indoor unit is blocked. 
•  Doors and windows are open, sunlight 

directly shine. 

•  Too much heat source. 
•  Leakage of water. 

•  Clean the heat exchanger. 
•  Clean the air filter. 
•  Eliminate all dirties and make 

air smooth. 

•  Close doors and windows. 
•  Make curtains in order to 

shelter from sunshine. 

•  Reduce heat source. 
•  AC cooling capacity reduces 

(normal). 

•  Check leakage. 

Low heating effect. 

•  Doors and windows not completely 

closed. 

•  Leakage of water. 

•  Use heating device. 
•  Close doors and windows. 
•  Check leakage. 

 

 

 

 

 

26

 

 

 

  Four-way Cassette DC Fan Coil Unit  

 

Содержание MUCS-20-W9

Страница 1: ...www mundoclima com Cassette 4 Ways FCU DC Service manual English CL04433 to CL04435 MUCS W9...

Страница 2: ...nal Appearance 3 2 Features 3 3 Product lineup 4 4 Accessories 5 5 Specifications 6 6 Capacity Table 7 7 Sound Levels 26 8 Dimension 26 9 Service Spaces 30 10 Wiring Diagrams 31 11 Troubleshooting 32...

Страница 3: ...high efficiency Wireless remote control with LED display wired control is optional Safety grill for safety maintenance Built in drain water pump with 750mm pumping head Optional extended drainage pan...

Страница 4: ...durable motor The motor bearing can operate 80 000 hours continuously and easy for maintenance Low noise Advanced 3 D spiral fan design reduces air resistance and operating sound The motor bearing wi...

Страница 5: ...t M6 4 Tubing Fittings 2 Soundproof insulation sheath Drainpipe Fittings 1 Out let pipe 1 Out let pipe sheath 1 Out let pipe clasp 5 Tightening band Remote controller Its Frame 1 Remote controller R05...

Страница 6: ...7 Panel Net dimensions W H D mm 950 45 950 950 45 950 Packing size W H D mm 1035 90 1035 1035 90 1035 Net weight kg 6 6 Gross weight kg 9 9 Body Net dimensions W H D mm 840 300 840 840 300 840 Packin...

Страница 7: ...1 21 27 27 19 6 93 3 06 1 49 38 84 6 89 3 61 1 48 38 51 6 86 4 15 1 47 38 18 6 82 4 69 1 47 37 86 6 79 5 22 1 46 37 54 20 7 89 3 65 1 7 48 61 7 86 4 19 1 69 48 21 7 82 4 73 1 68 47 82 7 78 5 27 1 67...

Страница 8: ...27 3 24 3 24 0 7 10 18 3 85 3 85 0 83 13 63 20 3 38 2 15 1 1 10 64 3 34 2 69 0 72 10 71 3 4 3 09 1 1 10 98 3 88 3 79 0 83 13 77 5 15 0 92 0 92 0 16 0 86 1 38 1 38 0 24 1 29 2 27 2 27 0 39 2 65 2 94 2...

Страница 9: ...22 85 6 7 6 31 1 44 24 82 7 35 7 35 1 58 29 07 19 8 98 3 97 1 93 40 84 8 93 4 69 1 92 40 48 8 89 5 4 1 91 40 12 8 84 6 11 1 9 39 77 8 8 6 8 1 89 39 42 20 10 25 4 74 2 2 51 23 10 2 5 46 2 19 50 8 10 1...

Страница 10: ...3 3 0 73 7 21 4 21 4 21 0 91 10 77 5 02 5 02 1 08 14 49 20 4 17 2 72 1 44 10 2 4 21 3 44 0 91 10 74 4 38 4 03 0 94 11 51 5 03 4 95 1 08 14 57 5 15 1 22 1 22 0 21 1 03 1 82 1 82 0 31 1 54 2 63 2 63 0 4...

Страница 11: ...1 95 37 53 9 43 8 74 2 02 40 15 10 27 10 18 2 21 46 48 19 12 67 5 59 2 72 66 32 12 58 6 57 2 7 65 58 12 5 7 53 2 68 64 84 12 42 8 48 2 67 64 12 12 34 9 42 2 65 63 4 20 14 39 6 63 3 09 82 52 14 3 7 6 3...

Страница 12: ...5 6 4 9 4 66 1 05 11 67 5 96 5 96 1 28 17 61 7 06 7 06 1 52 23 45 20 5 98 3 58 1 96 17 57 5 72 4 39 1 23 16 33 6 25 5 63 1 35 19 09 7 1 6 91 1 53 23 68 5 15 1 9 1 9 0 33 1 92 2 8 2 8 0 48 2 84 3 96 3...

Страница 13: ...62 0 38 5 04 5 98 0 35 4 24 5 33 0 31 3 46 4 66 0 27 2 59 55 5 10 5 1 83 70 77 9 88 1 72 63 65 9 27 1 62 56 89 8 66 1 51 50 5 8 9 85 1 07 28 02 9 23 1 25 05 8 62 0 94 22 24 8 01 0 87 19 59 10 9 4 0 8...

Страница 14: ...0 59 5 26 15 9 81 0 57 4 97 8 88 0 51 4 2 7 94 0 46 3 44 6 98 0 4 2 6 55 5 15 23 2 65 67 13 14 33 2 5 60 33 13 43 2 34 53 89 12 54 2 19 47 82 8 14 33 1 56 26 76 13 44 1 46 23 92 12 54 1 36 21 23 11 65...

Страница 15: ...10 15 0 59 7 9 01 0 52 4 86 7 62 0 44 3 07 5 7 0 33 2 17 55 5 16 94 2 95 115 9 15 93 2 78 104 13 14 93 2 6 92 99 13 93 2 43 82 46 8 15 82 1 72 45 82 14 81 1 61 40 9 13 81 1 5 36 26 12 81 1 39 31 88 10...

Страница 16: ...7 Sound Levels H M L dB A 44 40 34 MUCS 24 W9 MUCS 36 W9 48 44 41 49 43 39 MUCS 20 W9 19 Four way Cassette DC Fan Coil Unit...

Страница 17: ...MUCS 20 W9 20 Four way Cassette DC Fan Coil Unit MUCS 24 W9...

Страница 18: ...MUCS 36 W9 21 Four way Cassette DC Fan Coil Unit...

Страница 19: ...8 Dimension Model A B C D E F MUCS 20 W9 180 140 85 350 145 195 MUCS 24 W9 MUCS 36 W9 180 140 155 350 155 205 22 Four way Cassette DC Fan Coil Unit...

Страница 20: ...9 Service Spaces Model A B C 230 170 260 300 190 330 MUCS 20 W9 MUCS 24 W9 MUCS 36 W9 23 Four way Cassette DC Fan Coil Unit...

Страница 21: ...CN13 CN19 CN18 POWER IN 3 2 V1 1 N L V2 XT1 4 RED RED BLUE BLUE RED BLUE BLACK BLUE ONLY 4 PIPE ONLY 4 PIPE G Y ALARM CN3 L N POWER S4 1 2 ON ENC1 S2 1 2 3 4 ON S1 1 2 3 4 ON S3 1 2 3 4 ON ON OFF CN1...

Страница 22: ...ECTOR SWITCH OVER HEAT H AUXILIARY HEATER CS WATER LEVEL SWITCH PUMP PUMP MOTOR Notes 1 SW1 must be set as the Table B 2 Two control mode is only connected with a valve valve 1 Four control models are...

Страница 23: ...oller Wait for the comeback of power Switch on the power Replace the fuse Replace the batteries or check the controller Air flowing normally but completely can t cooling Temperature is not set correct...

Страница 24: ...top up to the set time The TIMER on indicator goes off after a lapse of certain time Check whether the timer operation is started when the TIMER ON is indicated on the display Up to the set time the a...

Страница 25: ...insulation tightly around the hole of the unit as shown The ends of the side plate and the inner insulation must be completely adhered without leaving any clearance along the circumference of the hol...

Страница 26: ...become loose because of concrete shrinking b After installing the body please fasten the installation paper board onto the air conditioner with bolts M6 12 to determine in advance the sizes and posit...

Страница 27: ...n floor or against the wall or on bulgy objects Never crash or strike it 1 Remove the air inlet grill a Slide two grid switches toward the middle at the same time and then pull them up Refer to fig 12...

Страница 28: ...ir in grid in the procedure of reversed order 6 Relocate the installation cover a Fasten the rope of installation cover on the bolt of the installation cover b Press the installation cover into the pa...

Страница 29: ...water receiver through the stow tube 2 Turn on the power and operate the air conditioner under the COOLING mode Listen to the sound of the drain pump Check whether the water is discharged well a lag...

Страница 30: ...in power distribution The distribution has to be of low impedance normally the required impedance reaches at a 32A fusing point 2 No other equipment has to be connected with this power line 3 For deta...

Страница 31: ...12 7 2 Wiring figure 34 Four way Cassette DC Fan Coil Unit...

Страница 32: ...e user s requirement install the remote controller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with t...

Страница 33: ...SAT 34 93 652 53 57 www mundoclima com C N POLES 249 P1 ESPA A SPAIN 34 93 446 27 80 08013 BARCELONA...

Отзывы: