SET
ENT
ENT
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
MS 1208
ºC
SCANNER
0 0 0 0
CH 1
www.multispanindia.com
Page - 1
MS-1208
OPERATING MANUAL
8 CHANNEL TEMP. SCANNER
MS-1208
Power Supply
Operating
Temperature
Relative
Humidity
100 to 250V AC,50/60 Hz, Approx 4VA
0°C To 55°C
Up to 95% RH Non Condensing
Model
Display
Size (mm)
Panel Cutout
Range
Input
96 (H) X 96 (W) X 50 (D) mm
92 X 92 mm
J Type: 0 To 600°C/K Type: 0 To 1200°C/
PT-100: -99 To 400°C (DP Selectable)
J,K,PT-100/3W Selectable
MS-1208
Technical Specification
Connection Diagram
Protection
Level
(As per request)
IP-65 (Front side) As per IS/IEC 60529 : 2001
UPPER:- 4 Digit 7 seg 0.56”, red LED Display
LOWER:- 3 Digit 7 seg 0.4”, red LED Display
-
-
-
-
-
-
-
-
18
14
19
13
20
12
21
11
22
10
23
24
1
2
3
4
5
6
7
8
9
16
17
15
+
+
+
+
+
+
+
+
T/C
T/C
T/C
T/C
T/C
PT-100/3W
PT-100/3W
PT-100/3W
PT-100/3W
PT-100/3W
T/C
T/C
T/C
PT-100/3W
PT-100/3W
PT-100/3W
CH-1
CH-4
CH-5
CH-3
CH-2
CH-6
CH-8
8 CHANNEL SCANNER (J,K, PT-100)
Range: ‘J’ : 0 To 600°C
‘K’ : 0 To 1200°C
PT-100/3W : -99 To 400°C (DP Selectable)
CH-7
AUX. SUPPLY
100 To
250V AC
~
100
250V AC
~
50/60 HZ
4VA
AUX. SUPPLY
100 To
250V AC
~
~
50/60 Hz
4VA
!
100
250V AC
L
N
1) Do all connection as shown in connection diagram.
2) To enter in parameter menu, press set key.
Configure: 1. Scan time
2. Sensor Selection ( J, K or PT-100 Selectable)
3. Skip or unskip channel
4. DP selection for pt-100 only.
3) If needed to add offset,
press + together for 5 Sec.
Set offset for each channel if required.
Off set range will be -25°C to + 25°C.
4) Press & Hold Key for continuous scrolling or manual scrolling.
5) In hold mode use & Key to select next channel.
Procedure