background image

SET

ENT

ENT

  CH1

  CH2

  CH3

  CH4

  CH5

  CH6

  CH7

  CH8

  MS 1208

ºC

SCANNER

0 0 0 0

CH 1 

www.multispanindia.com

Page - 1

MS-1208

OPERATING MANUAL 
8 CHANNEL TEMP. SCANNER             

MS-1208

 Power Supply

  Operating
Temperature

  Relative
 Humidity

100 to 250V AC,50/60 Hz, Approx 4VA

0°C To  55°C

Up to 95% RH Non Condensing

Model

Display

Size (mm)

Panel Cutout

 
      Range

 
      Input

96 (H) X 96 (W) X 50 (D) mm

92 X 92 mm

J Type: 0 To 600°C/K Type: 0 To 1200°C/
PT-100: -99 To 400°C (DP Selectable)

J,K,PT-100/3W Selectable

MS-1208

Technical Specification

Connection Diagram

   Protection
      Level

   
      (As per request)

IP-65 (Front side) As per IS/IEC 60529 : 2001  

UPPER:- 4 Digit 7 seg 0.56”, red LED Display
LOWER:- 3 Digit 7 seg 0.4”, red LED Display

-

-

-

-

-

-

-

-

18

14

19

13

20

12

21

11

22

10

23

24

1

2

3

4

5

6

7

8

9

16

17

15

+

+

+

+

+

+

+

+

T/C

T/C

T/C

T/C

T/C

PT-100/3W

PT-100/3W

PT-100/3W

PT-100/3W

PT-100/3W

T/C

T/C

T/C

PT-100/3W

PT-100/3W

PT-100/3W

CH-1

CH-4

CH-5

CH-3

CH-2

CH-6

CH-8

8 CHANNEL SCANNER (J,K, PT-100)

Range:          ‘J’ : 0 To 600°C
                     ‘K’ : 0 To 1200°C
      PT-100/3W : -99 To 400°C (DP Selectable)

CH-7

 AUX.  SUPPLY

100 To
250V AC

~

 

100 
250V AC

~

 

50/60 HZ
4VA

 AUX.  SUPPLY

100 To
250V AC

~

~

 

50/60 Hz
4VA

!

100
250V AC

L

N

1) Do all connection as shown in connection diagram. 
2) To enter in parameter menu, press set key.
     Configure:   1. Scan time
                           2. Sensor Selection ( J, K or PT-100 Selectable)
                           3. Skip or unskip channel
                           4.  DP selection for pt-100 only.
3) If needed to add offset, 

press     +     together for 5 Sec.

     Set offset for each channel if required.
     Off set range will be -25°C to + 25°C. 
  

 

4)  Press & Hold      Key for continuous scrolling or manual scrolling.
5)  In hold mode use     &     Key to select next channel.  
     

Procedure