MULTISPAN AVH-14N Скачать руководство пользователя страница 1

Multispan Control Instruments Pvt Ltd

72/B, Phase 1, GIDC Estate, Vatva, Ahmedabad-382445, Gujarat, India.

www.multispanindia.com

+91-9978991483

[email protected]

AVH 14N

User Manual

ENVIRONMENT CONDITION:

INPUT:

Direct Voltage AC

30 to 300V(L - N)
50 to 500V(L - L)

Burden

Voltage AC

Current AC

Burden

Primary CT Ratio

Secondary Current AC

Overload

Frequency

 Up  to 6A continuous

45.0 to 65.0 Hz

< 0.2VA

5 to 6000 Amp selectable 

< 0.2VA

50mA to 5 Amp Direct 

3 Phase - 3 Wire, 3 Phase - 4 Wire

(Network Selection)

Supply Voltage

100 to 270V AC, 50/60 Hz

Power Consuption

4VA @ 230 AC MAX

AUXILIARY SUPPLY:

Size (mm)

Panel Cutout (mm)

96 (H) X 96 (W) X 52 (D) mm
92 (H) X 92 (W) mm

DIMENSION:

Display

Upper: 6 Digit, 7 Seg 0.40”,RED LED For KWH

LOWER: 4 Digit, 7 Seg 0.40”,RED, 3 Line
            

Keys

SET/ENT, INC, DEC, RESET

DISPLAY AND KEYS:

Technical Specification

Protection Level
(As Per Request) 

IP-65 (Front side) As per IS/IES 
60529 : 2001

Operating Temperature

0°C To 55°C

Relative Humidity

Up to 95% RH Non Codensing

Terminal Diagram

* The maximum demand value is the maximum average 
    value of the instantaneous power during a defined time
    interval set in MD Time parameter. The default value of 
    MD time is 15 minutes, which is selectable.

Maximum Demand

To select connection press           key and power on the 
instrument.To save the connection power off the
instrument.

Wiring Connection

RESET

  Change by        
            key

  3 Phase/3wire   3 Phase/4wire

  Upper Display

Lower Display

RESET

Parameters

Parameter Display

Phase Neutral Voltage (Vpn) 

30 - 300 V 

50mA -5A (Direct without CT)

50 - 500 V

0.000 - 9999 KW
0.000 - 9999 KW
000.000 - 999999 KWh

000.000 - 999999 KVAh

000.000 - 999999 KVArh

0.10 - 1.00

0.10 - 1.00

0.000 - 9999 KVA

9999.59 Hrs/Min.

0.000 - 9999 KVAr

30

00 RPM

45 - 65 Hz

9999.59 Hrs/Min.

Line CURRENT ( ~A )

Line Voltage (Phase-to-Phase) (Vpp)

Active Power ( KW ) Total
Active Power per Phase(KW)
Active Energy ( KWH ) 

Apparent Energy ( KVAh ) 

Reactive Energy ( KVArh) 

Power Factor ( PF ) Average
Power Factor per phase ( PF ) 

Apparent Power (KVA )

Load hours

Reactive Power ( KVAr )

RPM

Frequency ( Freq )

No load hours

Measurement Range

MD KW

MD KVA

MD KVAr

0.000 - 9999 KW

0.000 - 9999 KVA

0.000 - 9999 KVAr

  C O n e

  C O n e

  3 P 3 w

  3 P 4 w

1

2

3

4

7

8

9

12

13

14

10

11

5

16

17

18

19

20

6

15

S1

S1

S1

S2

S2

S2

L1

L2

L3

Range:

Current: 50mA To 5A AC               

Voltage (L-L) : 50-520V AC

(L-N) : 30-300V AC

Accuracy:

For Voltage & Current 
Class: 0.5
For Power & Energy 
Class: 1.0

System:
                          

3Ph-4W/3Ph-3W

L

N

!

Made in India

www.multispanindia.com

100  
270V AC
    

50/60 Hz
4VA

CAT III

V

L

1

V

L

2

V

L

3

N

Model:

 

AVH 14N-A2-00

Отзывы: