![MTU 20V4000G44F Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/mtu/20v4000g44f/20v4000g44f_operating-instructions-manual_1852704049.webp)
5.2 Putting into operation after scheduled out-of-service-period
Preconditions
☑
Engine is stopped and starting disabled.
Putting into operation
Item
Action
Lube oil system
Check engine oil level (→ Page 153);
Coolant circuit
Check engine coolant level (→ Page 160).
Check charge-air coolant level (→ Page 183).
Coolant circuit
Heat engine coolant with coolant preheater.
Fuel prefilter
Drain water (→ Page 129), (→ Page 131).
Monitoring system
Carry out lamp test (see manufacturer's documentation).
Engine/generator control
system
Switch ON;
Select operating mode, e.g.: MANUAL, AUTOMATIC OPERATION.
MS15058/04E 2018-12
| Operation | 47
TIM-ID: 0000074303 - 001