Brief Operation Manual for Safe Use, Document Number: 551409 Revision A, 04/13 (US)

Safety 

Instructions

Model MR Brief Operation Manual for Safe Use

Safety Instructions

Safety instructions

The Brief Operation Manual for Safe Use contains safety instructions. For further information do consult the Operation and Installation Manual, 

document no.: 550720, available on the Level Product CD, part no.: 550766 supplied with your level transmitter or cost free download at 
www.mtssensors.com.

INTENDED USE

The Level Plus® Model MR liquid level transmitter is used for continuous measurement of product level, interface level, and/or temperature 

of liquids in containers in hazardous areas.

INSTALLATION, COMMISSIONING AND OPERATION

•   The liquid level transmitter may only be installed, connected, operated and maintained by trained technical personnel. The technical 

personnel must strictly adhere to the Operating Instructions, prevailing standards, legal regulations and certificates (depending on 
application).

•    If the Brief Operating Manual for Safe Use does not provide sufficient information, you must read the Operation and Installation 

Manual. There, you can find detailed information on the device.

•   The operator may only perform direct replacement of like components manufactured by MTS that are explicitly permitted in the 

Operating Instructions.

•   Do not operate damaged products and secure them against unintentional commissioning. Mark the damaged product as being 

defective.

•   If faults cannot be rectified, the products must be taken out of service and secured against unintentional commissioning.
•   The product is designed to meet state-of-the-art safety requirements, has been tested and left the factory in a condition in which it 

is safe to operate. Relevant regulations and European standards have been observed.

•   As the user, you are responsible for complying with the following safety conditions:

- Installation instructions
- Local prevailing standards and regulations

•   Only use the product according to its specification.

SPECIAL CONDITIONS FOR USE IN EXPLOSION-HAZARDOUS AREAS

•   Model MR sensors may only be connected to certified intrinsically safe circuits (Ex ia or Ex ib).
•   The electronics housing is to be installed in zone 1 (category 2G, EPL Gb}. The sensor pipe/hose may be installed in zone 0 

(category 1, EPL Ga} if not restricted below.

•   Equipotential bonding shall be installed inside and outside the hazardous area along the cable for supply and data.
•   Float usage:

-  Metallic floats may only be used if they have a weight offset (asymmetric weight distribution). 
-  Metallic floats on non-metallic pipes may not  be used.
-  Aluminum floats may not be used.

•   Plastic floats may only be installed in hazardous areas which require apparatus of category 1G (for zone 0} with explosion group IIA.  

Plastic floats may not be used on non-metallic pipes.

•   Sensors with flexible measuring hoses: 

-  The hose has to be mechanically protected from external impacts which may affect its function as separation wall.
-  Avoid kinking or bending the flexible hose in less than 16 inch (406 mm) diameter.

Содержание Level Plus M-Series MR

Страница 1: ...Level Plus Liquid Level Sensors With Temposonics Technology M Series Model MR Analog Transmitter SENSORS Document Part Number 551409 Revision A Brief Operation Manual For Safe Use...

Страница 2: ...MTS Sensors Level Plus Liquid Level Sensors M Series Model MR Analog Transmitter Brief Operation Manual for Safe Use Document Number 551409 Revision A 04 13 US...

Страница 3: ...http www mtssensors com MAILING AND SHIPPING ADDRESS MTS Systems Corporation Sensors Division 3001 Sheldon Drive Cary North Carolina 27513 USA CUSTOMER SERVICE Tel 1 800 457 6620 Fax 1 800 498 4442 E...

Страница 4: ...s Intended Use 1 Installation commissioning and operation 1 Special conditions for use in explosion hazardous areas 1 Model number identification Model number configuration 2 Marking 3 Entity paramete...

Страница 5: ...ainst unintentional commissioning Mark the damaged product as being defective If faults cannot be rectified the products must be taken out of service and secured against unintentional commissioning Th...

Страница 6: ...ible w bottom fixing hook stainless steel only C Sanitary T bar TB J Flexible w bottom fixing weight stainless steel only D Sanitary drain in place DP K Flexible w bottom fixing magnet stainless steel...

Страница 7: ...d product E Engineering special not affecting agency controlled parts or features Marking Model Housing Type 5 Material of Construction 8 ATEX marking MR F G H J K 1 2 3 II 1 2 G Ex ia IIA T4 Ga Gb A...

Страница 8: ...tallation Figure 1 Safety barrier connections Non Hazardous Area Hazardous Area Certi ed Safety Barriers 24 Vdc Supply Voltage I A 4 20 mA I S Ground connection Transmitter Model MR Brief Operation Ma...

Страница 9: ...ows the float to stay in contact with the pipe to prevent the buildup of electrostatic charge For detailed information about floats refer to the Accessories Catalog MTS part number 551103 Non metalic...

Страница 10: ...s Liquid Level Sensors M Series Model MR Analog Transmitter Brief Operation Manual for Safe Use Document Number 551409 Revision A 04 13 US 6 Model MR Brief Operation Manual for Safe Use EC Declaration...

Страница 11: ...MTS Sensors Level Plus Liquid Level Sensors M Series Model MR Analog Transmitter Brief Operation Manual for Safe Use Document Number 551409 Revision A 04 13 US 7...

Страница 12: ...ww mtssensors com for the latest product information Document Part Number 551409 Revision A 04 13 US MTS Sensor Technologie GmbH Co KG Auf dem Sch ffel 9 D 58513 L denscheid Germany Tel 49 2351 9587 0...

Отзывы: