MSA AUER
MSA
Maintenance and Service
SUPREMATouch
97
US
6.8
System Failure Messages
No.
Failure Mes-
sage Text
Module
Appears in
case of
Disappears
in case of
Error
LED
Fail
LED
Info 1
[BYTE]
Info 2
[DWORD]
Remarks/ Remedial action
1
dynamic mem-
ory overflow
All
Stack overflow
or stack under-
flow detected
Restart
X
X
Task ID
Memory ad-
dress
Generally software problems
[e.g. wrong stack dimensions]
Perhaps sequence error
to No. 2,3 or 6
2
error in work
memory
All
RAM failure de-
tected [Self-test]
Whole RAM
tested fail-
ure-free [af-
ter approx.
24 h]
X
X
Bit pattern
fault bits
Memory ad-
dress
Hardware defect: exchange
module
3
error in pro-
gram memory
All
ROM failure de-
tected [Self-test]
Whole ROM
tested fail-
ure-free [af-
ter approx.
24 h]
X
X
1
→
found
during sys-
tem start;
0
→
other-
wise
loWord
→
CRC found;
hiWord
→
CRC should
be
Hardware defect: exchange
module
4
internal time-
out
All
Life sign of at
least one task is
missing
All tasks
gave life
sign in time
X
X
Nominal val-
ue of task
flags [8 low-
est Bits]
loWord
→
task flags is;
hiWord
→
task flags
should be
Perhaps sequence error of
CAN bus failure. Check bus.
5
data lost on
bus
MDA,
MGO,
MAO
CAN controller
detects overflow
CAN Con-
troller in nor-
mal mode
X
X
Always 0
Always 0
Perhaps not correctly termi-
nated bus or modules with
wrong bitrate at the bus.
[Green CAN-LED indicates
the status of the bus.]
May also be defect hardware.
6
fatal internal
error
All
Exception Inter-
rupt [e.g. write
access to ROM,
invalid memory
address...]
Restart
X
X
Exception
number
Memory ad-
dress
Hardware defect: exchange
module
Perhaps sequence error to
No. 1, 2 or 3
7
buffer overflow MCP,
MDO,
MDA,
MBC
Overflow of the
internal process-
ing queues.
Restart
X
X
Queue
number
Queue Sta-
tus
Perhaps in combination with
No. 4 at system overload or
sequence error to CAN bus
failures
8
communica-
tion error on
bus
MCP,
MDO
Error during
SDO transfer
[transfer of con-
figuration and
parameter data]
SDO trans-
fer success-
fully ended
X
X
CAN-I/O er-
ror code
Additional
data [error
code de-
pended]
Perhaps CAN-bus failure:
check Bus.
Check MCP and MDO for in-
compatible software status.
May occur when hot plugging
modules.
9
system error of
configuration
memory
MCP,
MDO,
MBC
Error on access-
ing flash memo-
ry which
contains param-
eter and configu-
ration data
Restart
X
X
Flash error
code
Additional
data [error
code de-
pended]
Hardware defect: exchange
module
Perhaps in combination with
No. 10 or 15.
10
error in config-
uration memo-
ry
MCP,
MDO,
MBC
Flash error de-
tected [Self-test
of the configura-
tion and param-
eter memory]
Whole flash
tested error-
free [after
approx.
24 h]
X
X
Always 0
Always 0
Hardware defect: exchange
module
11
data lost at se-
rial communi-
cation
MDO
Error at serial
communication
Restart
X
X
Interface
number
loWord
→
number of
characters;
hiWord
→
status
Data lost at PC or printer inter-
face: Check cables
Perhaps hardware defect: ex-
change MDO module
12
node guarding
error detected
MCP,
MDO
Module does not
respond to
node- guarding,
or does not send
any heartbeat
All nodes re-
spond again
X
X
ID of node
that doesn't
respond
If the node in
info 1 is an
MDA and info
2 is not 0, this
is the MAI
number
CAN-Bus failure, module de-
fect or missing: Check bus
and modules
MGO,
MAO
X
X
Always 0
Time in sys-
tem-ticks
no output data was received
for a certain time: check bus
and MCP/MDO modules
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...