Installation
10.1 General Information
Installation Instructions for Following the EMC Directives
The devices of MSA have been developed and tested in accordance with the EMC Directives
2004/108/EG and 93/68/EEC and the corresponding standards EN 50270. The requirements of
the EMC Directives can only be met by following the manufacturer’s installation instructions. This
applies only to tested devices and systems of the manufacturer.
General Instructions on the Installation of Tested Devices and Systems of MSA AUER
GmbH to ensure that the EMC Directives are followed
-
For the connection of the various devices to the power supply system a clean ground or clean
potential ground must be provided.
-
An appropriate supply voltage free of feedback to the external source in accordance with the
EMC Directives must be used.
-
If the devices are supplied from a direct voltage (dc) source, the supply cable must be
screened.
-
Screened cable is to be used to connect the sensors.
-
Control cables must be screened (reset, acknowledge, measurement current output, printer,
etc.).
-
Screened cable must have at least 80% coverage by the screening.
-
Control and sensor cables must be laid physically apart from power supply cables.
-
Screened cables must be laid in one piece. If it should prove necessary to extend a cable by
way of a terminal box, the terminal box must be screened, and the connections in the box must
be kept as short as possible.
-
Unscreened cables and cables from which the insulation has been stripped must be as short
as possible and must be laid without loops to the appropriate terminal posts.
-
External devices that are operated by the gas warning units (horns, contactors, pumps, motors,
etc.) must be radio-screened and follow the EMC Directives.
-
If the EMC filters of the device are physically remote, the power supply cable between the filter
and the device must be screened.
-
If additional high-voltage surge protection measures are required an appropriate high-voltage
protection filter, approved by MSA AUER GmbH, must be installed in the sensor cable.
Instruction on Meeting the EMC Requirements on the SUPREMA Control System
To meet the EMC product standard EN 50270 (Electromagnetic Compatibility. Electrical appara-
tus for the detection and measurement of combustible gases, toxic gases or oxygen), the following
points must be observed:
Содержание SUPREMA Touch
Страница 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Страница 7: ...SUPREMATouch 6 Contents MSA US...
Страница 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Страница 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Страница 304: ...MSA AUER MSA Dimensions SUPREMA 303 GB 16 2 Rail mounted Modules MRO 8 TS Module MRO 16 TS Module...
Страница 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Страница 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Страница 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...