MSA fieldserver ProtoCarrier Скачать руководство пользователя страница 1

Operating Manual

ProtoCarrier Start-up Guide

Revision: 1.B

Document No.:T18609

Print Spec: 10000005389 (F)

MSAsafety.com

Содержание fieldserver ProtoCarrier

Страница 1: ...Operating Manual ProtoCarrier Start up Guide Revision 1 B Document No T18609 Print Spec 10000005389 F MSAsafety com...

Страница 2: ...rt Milpitas CA 95035 U S Support Information 1 408 964 4443 1 800 727 4377 Email smc support msasafety com EMEA Support Information 31 33 808 0590 Email smc support emea msasafety com For your local M...

Страница 3: ...2 Navigate to the Login Page 13 6 Setup Web Server Security 14 6 1 Login to the FieldServer 14 6 2 Select the Security Mode 16 6 2 1 HTTPS with Own Trusted TLS Certificate 17 6 2 2 HTTPS with Default...

Страница 4: ...1 Change Security Mode 30 10 4 2 Edit the Certificate Loaded onto the FieldServer 31 10 5 Change User Management Settings 32 10 5 1 Create Users 33 10 5 2 Edit Users 34 10 5 3 Delete Users 35 10 5 4 C...

Страница 5: ...d driver supplements Check the MSA Safety website for technical support resources and documentation that may be of assistance The ProtoCarrier is cloud ready and connects with MSA Safety s Grid See Se...

Страница 6: ...ecord Identification Data 2 Connect the ProtoCarrier to the field protocol port and customer s port to the ProtoCarrier s RS 485 interface Section 3 4 Wiring Field Port to RS 485 BMS Network 3 Connect...

Страница 7: ...3 Interfacing ProtoCarrier to Host OEM Device 3 1 ProtoCarrier FPC C34 and FPC C35 Showing Connection Ports ProtoCarrier Start up Guide 7...

Страница 8: ...3 pins for this as currently shown 3 2 Device Connections to ProtoCarrier ProtoCarrier 6 Pin Phoenix connector for RS 485 Devices The 6 pin Phoenix connector is the same for ProtoCarrier FPC C34 BACn...

Страница 9: ...the other low i e far away from the decision point of the logic In the RS 485 carrier the bias resistor is 510 ohms which is in line with the BACnet spec It should only be enabled at one point on the...

Страница 10: ...ier power jumper is set to position A by default but can be changed to position B for other power supply requirements Position A The gateway makes use of a full wave rectifying bridge Can be used for...

Страница 11: ...position left side If more than one RS 485 device is connected to the network then the field bias resistor switch needs to be enabled to ensure proper communication See image above for the orientation...

Страница 12: ...nt Draw Type ProtoCarrier Family 12VDC VAC 24VDC VAC 30VDC FPC C34 C38 Typical 170mA 110mA 90mA FPC C34 C38 Maximum 220mA 140mA 115mA FPC C35 C39 Typical 210mA 110mA 90mA FPC C35 C39 Maximum 260mA 140...

Страница 13: ...dows icon and type in Control Panel Click Control Panel click Network and Internet and then click Network and Sharing Center Click Change adapter settings on the left side of the window Right click on...

Страница 14: ...ear as untrusted This will cause the following pop up windows to appear When the Web Server Security Unconfigured window appears read the text and choose whether to move forward with HTTPS or HTTP Whe...

Страница 15: ...he Password found on the label of the FieldServer NOTE There is also a QR code in the top right corner of the FieldServer label that shows the default unique password when scanned NOTE A user has 5 at...

Страница 16: ...ch mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Section 10 4 Change Web Server Security Settings After...

Страница 17: ...will appear under the mode selection Copy and paste the Certificate and Private Key text into their respective fields If the Private Key is encrypted type in the associated Passphrase Click Save A Re...

Страница 18: ...ettings must be checked because there is a problem with device communications All the active profiles must show the correct Node ID s before proceeding NOTE If multiple devices are connected to the Pr...

Страница 19: ...ted to the new IP Address of the FieldServer before the webpage will be accessible again Unplug Ethernet cable from PC and connect it to the network switch or router Record the IP Address assigned to...

Страница 20: ...ble straight through or cross over between the PC and ProtoCarrier The default IP Address for the ProtoCarrier is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and ProtoCarrier are on different...

Страница 21: ...of ProtoCarrier fserver xif Example 192 168 1 24 fserver xif If the web browser prompts to save the file save the file onto the PC If the web browser displays the xif file as a web page save the file...

Страница 22: ...rver Toolbox zip via the MSA Safety website Extract the executable file and complete the installation Connect a standard Cat 5 Ethernet cable between the user s PC and ProtoCarrier Double click on the...

Страница 23: ...ieldServer Toolbox to connect to the FieldServer Click on Diagnostics and Debugging Button then click on view and then on connections If there are any errors showing on the Connection page refer to Se...

Страница 24: ...us TCP IP side To fix check the following Visual observations of LEDs on ProtoCarrier Section 9 5 LED Functions Check device address Verify wiring Verify all the Modbus TCP IP devices were discovered...

Страница 25: ...he Navigation panel Open the FieldServer Toolbox software and click the diagnose icon of the desired device Go to Full Diagnostic and select the capture period Click the Start button under the Full Di...

Страница 26: ...ion PWR The power light should always show steady green when connected to a functioning power source RX The RX LED will flash when a message is received on the serial port on the 6 pin connector If th...

Страница 27: ...d side do the following a Click on Setup b Click on File Transfer c Click on the General tab 5 In the General tab click on Choose Files and select the web img file extracted in step 1 6 Click on the o...

Страница 28: ...mple 192 168 1 24 prof1b csv Press the enter key and save the file Open the file and go to the server side map descriptors section The map_descriptor_name data_array_name and data array_offset will be...

Страница 29: ...p NOTE Any changes will require a FieldServer reboot to take effect Navigate from the ProtoCarrier landing page to the FS GUI by clicking the blue Diagnostics text on the bottom of the screen Click Se...

Страница 30: ...urity in the Navigation panel Click the Mode desired If HTTPS with own trusted TLS certificate is selected follow instructions in Section 6 2 1 HTTPS with Own Trusted TLS Certificate Click the Save bu...

Страница 31: ...ailable if the security mode was previously setup as HTTPS with own trusted TLS certificate Click Security in the Navigation panel Click the Edit Certificate button to open the certificate and key fie...

Страница 32: ...instructions see the FieldServer Recovery Instructions document If the default unique password is lost then the unit must be mailed back to the factory NOTE Any changes will require a FieldServer reb...

Страница 33: ...ls are hashed and salted NOTE The password must meet the minimum complexity requirements An algorithm automatically checks the password entered and notes the level of strength on the top right of the...

Страница 34: ...icon next to the desired user to open the User Edit window Once the User Edit window opens change the User Security Group and Password as needed Click Confirm Once the Success message appears click O...

Страница 35: ...10 5 3Delete Users Click the trash can icon next to the desired user to delete the entry When the warning message appears click Confirm ProtoCarrier Start up Guide 35...

Страница 36: ...al login password for the FieldServer as needed NOTE The password must meet the minimum complexity requirements An algorithm automatically checks the password entered and notes the level of strength o...

Страница 37: ...and network connections Click the Add Rule button to add a new row and set a new Destination Network Netmask and Gateway IP Address as needed Set the Priority for each connection 1 255 with 1 as the...

Страница 38: ...ved UKCA compliant LonMark Certified Power Requirements 9 30VDC or 12 24VAC Physical Dimensions 11 5 cm L x 8 3 cm W x 4 1 cm H 4 5 x 3 2 x 1 6 in Weight 0 2 kg 0 4 lbs Operating Temperature 20 to 70...

Страница 39: ...ited to the expected operating temperature range Meet the current and voltage rating for the FieldServer Furthermore the interconnecting power cable shall Be of length not exceeding 3 05m 118 3 Be con...

Страница 40: ...been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases MSA Safety s responsibilit...