11.4 Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating the EZ Gateway.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.
•
The interconnecting power connector and power cable shall:
◦
Comply with local electrical code
◦
Be suited to the expected operating temperature range
◦
Meet the current and voltage rating for the FieldServer
•
Furthermore, the interconnecting power cable shall:
◦
Be of length not exceeding 3.05m (118.3”)
◦
Be constructed of materials rated VW-1, FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a
Restricted Access Area requiring a key or a special tool to gain access.
•
This device must not be connected to a LAN segment with outdoor wiring.