8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
168
4349315/00 EN
VACUTAP® VR®
Installing electrics for protective relay
The protective relay's dry-reed magnetic switch is supplied in the standard
version as either an NC or NO contact. Other contact equipment can be sup-
plied as special versions and is shown in the dimensional drawing provided.
1.
Insert cable connection (RS 2001, 2001/V, 2001/H, 2001/E, 2001/5,
2001/R) or adapter (RS 2003 und RS 2004) in the tapped hole which
seems to be in the most favorable position.
Figure 223: Cable bushing
2.
Seal open tapped hole with MR dummy plug.
Figure 224: Dummy plug
8.2.3