6 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
175
5293079/01 EN
VACUTAP
®
VM-Ex
6.1.1.2 Bleeding suction pipe on pipe connection S
1. Remove screw cap from pipe connection S.
Figure 208: Screw cap
2.
NOTICE!
An incompletely bled suction pipe significantly impairs the insu-
lation capability of the on-load tap changer to ground. Open vent screw
and bleed suction pipe completely.
3. Close vent screw.
4. Seal vent screw with screw cap.
6.1.2 Grounding the on-load tap-changer
If necessary, reduce the stated tightening torque according to the grounding
line used.