Status of the motor-drive unit (motor protective switch, motor is run-
ning)
–
Bandwidth monitoring
–
Function monitoring
–
Limit value monitoring (voltage, current, power, phase angle)
▪
Cooling system control
–
2, 4 or 6 cooling stages, can be individually parameterized
–
Load-dependent mode (for early activation of cooling stages)
–
Periodic mode (for regular activation of cooling stages)
–
Alternating mode (for equal loading of similar cooling stages)
▪
Cooling stage monitoring (2, 4 or 6 cooling stages)
▪
DGA
–
Up to 10 gases via analog input
–
Relative moisture in oil via analog input
Design
Depending on the order, the device is either designed as a 19-inch plug-in
housing or as individual components for assembly on a cap rail. The device's
individual assemblies are described in the following section.
Figure 2: 19-inch plug-in housing