6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
132
5163667/00 EN
TRAFOGUARD® ISM®
Figure 94: General cooling
To configure periodic mode, proceed as follows:
1.
Go to
Settings > Parameters > General cooling
.
2.
Select the parameter you want.
3.
Select the option you want from the list box or enter the desired value.
4.
Press the
Accept
button to save the modified parameter.
Configuring alternating mode
If the transformer is equipped with several similar cooling stages, you can
run the stages in alternating mode. In alternating mode, each of the cooling
stages is run in turn to evenly distribute the load of the cooling stages. You
can activate/deactivate alternating mode individually for every cooling stage
(Configuring cooling stages [
Only use alternating mode for similar cooling stages.
Example: If you activate alternating mode for 2 cooling stages and set a
change interval of 1,000 h, then cooling stage 1 is switched off after 500 h
and cooling stage 2 is switched on. After 500 h cooling stage 2 is switched
off and cooling stage 1 is switched on etc.
The following parameters are available to configure alternating mode:
▪
Activate alternating mode
▪
Change interval: Period after which the cooling stage is to be changed.
6.10.4