6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
103
5163667/00 EN
TRAFOGUARD® ISM®
Parameter
Option
Phase angle correction
-
UI measuring channels
3-phase measurement (channels 1,
2, 3)
Measurement mode
Phase-neutral
Table 21: Circuit H
Setting voltage-transformer circuit
You can use this parameter to set your voltage transformer's circuit. You can
select the following options:
Option
Description
1 Ph phase voltage
Measurement in 1-phase grid be-
tween the conductor and neutral
conductor.
3 Ph differential voltage
Measurement in 3-phase grid be-
tween 2 conductors
3 Ph phase voltage
Measurement in 3-phase grid be-
tween conductor and neutral con-
ductor
Table 22: Voltage-transformer circuit
To set the voltage-transformer circuit, proceed as follows:
1.
Go to
Settings > Parameters > Transformer data > Voltage-trans-
former circuit
.
2.
Select the option you want.
3.
Press the
Accept
button to save the modified parameter.
Setting current-transformer circuit
You can use this parameter to set the circuit for your current transformer.
You can select the following options:
Option
Description
1 Ph phase current
Measurement of phase current in 1-
phase grid.
3 Ph total current
Measurement of differential current
in 3-phase grid.
3 Ph phase current
Measurement of phase current in 3-
phase grid.
Table 23: Current-transformer circuit
To set the current-transformer circuit, proceed as follows:
1.
Go to
Settings > Parameters > Transformer data > Current-trans-
former circuit
.
2.
Select the option you want.
Содержание TRAFOGUARD ISM
Страница 1: ...Monitoring System TRAFOGUARD ISM Operating Instructions 5163667 00 EN ...
Страница 222: ......
Страница 223: ......