6 Functions and settings
Maschinenfabrik Reinhausen 2014
85
2374092/04 EN
TAPCON® 260
Parameter set
Measured value display
Primary
voltage
Secon-
dary
voltage
Primary
current
Trans-
former
connec-
tion
Voltage (main
screen)
Current
(main screen)
Current (info
screen)
-
Yes
-
-
Secondary volt-
age [V]
-
Secondary cur-
rent [% of con-
nection]
Yes
Yes
-
-
Primary voltage
[kV]
-
Secondary cur-
rent [% of con-
nection]
Yes
Yes
Yes
-
Primary voltage
[kV]
Primary cur-
rent [A]
Secondary cur-
rent [% of con-
nection]
Yes
Yes
-
Yes
Primary voltage
[kV]
-
Secondary cur-
rent [A]
Yes
Yes
Yes
Yes
Primary voltage
[kV]
Primary cur-
rent [A]
Secondary cur-
rent [A]
Table 19: Influence of transformer data on measured value display
Setting the primary transformer voltage
This parameter can be used to set the primary transformer voltage in kV.
When you are setting the primary transformer voltage, the device shows the
primary voltage rather than the secondary voltage in the main screen and
you can also set the control parameters in kV.
If a setting of 0 kV is chosen, no primary transformer voltage is displayed.
To set the primary transformer voltage, proceed as follows:
1.
>
Configuration >
Transformer data.
ð
Primary voltage.
2.
Press
to highlight the decimal place.
ð
The decimal place is defined and the value can be changed.
3.
Press
to highlight the position.
ð
The desired position is highlighted and the value can be changed.
4.
Press
to increase the value or
to reduce it.
5.
Press
.
ð
The primary transformer voltage is set.
Setting the secondary transformer voltage
This parameter can be used to set the secondary transformer voltage in V.
6.9.1
6.9.2