6 Functions and settings
Maschinenfabrik Reinhausen 2014
70
2374092/04 EN
TAPCON® 260
Figure 45: Response to value falling below limit value
1
+ B %: Upper limit
7
U
actual
: Measured voltage
2
U
desired
: Desired value
A
Value falls below limit value
3
- B %: Lower limit
B
Undervoltage U<
message is
displayed
4
Set limit value for undervolt-
age U<
C
Voltage falls below 30 V
5
Limit value for suppressing
alarms below 30 V
D
Voltage exceeds 30 V again
6
Set signaling delay time for
limit value for undervoltage
U<
E
Value exceeds limit value
Setting undervoltage V< as %
You can use this parameter to set the limit value as a relative value (%). This
limit value refers to the desired value you have set. If you want to use the set
relative value as the limit value, go to
Absolute limit values
and activate
the
Off
selection.
To set the limit value for undervoltage V<, proceed as follows:
1.
>
Parameter >
Limit values > Press
until the desired
parameter is displayed.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The limit value is set.