6 Functions and settings
Maschinenfabrik Reinhausen 2014
58
2374092/04 EN
TAPCON® 260
You can use this parameter to assign the freely configurable output relay
messages which are to be issued. You can assign the following messages:
Parameter
Messages
Off
No function selected
Master/Follower
Assign
Master/Follower
message.
Local/Remote
Assign
Local/Remote
message.
Undervoltage
Assign
Undervoltage blocking
message.
Overvoltage blocking
Assign
Overvoltage blocking
message.
Desired value 2
Assign
Desired value 2
message.
Desired value 3
Assign
Desired value 3
message.
MD operating time I>
Pulse message triggered. Assign Motor runtime
exceeded
message.
MD operating time D>
Continuous signal is active. Assign Motor run-
time exceeded
message.
Bandwidth <
Assign
Value fallen below bandwidth
message.
Bandwidth >
Assign
Bandwidth exceeded
message.
Table 11: Possible messages for output relays
To assign functions to the output relays, proceed as follows:
1.
Press
>
Configuration >
General >
until the desired
parameter is displayed.
ð
IO1-X1:25/26 or IO1-X1:23/24.
2.
Press
or
until the desired function appears in the display.
3.
Press
.
ð
The function is assigned.
Dimming display
You can use this parameter to activate or deactivate automatic display dim-
ming. You can select the following options:
▪
On: The display is automatically dimmed if no key is pressed for 15 mi-
nutes. The display returns to full brightness by pressing any key.
▪
Off: Automatic display dimming is deactivated.
Activating this function extends the display's service life.
To activate/deactivate automatic display dimming, proceed as follows:
6.3.8