![MR TAPCON 260 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363043.webp)
5 Commissioning
Maschinenfabrik Reinhausen 2014
43
2374092/04 EN
TAPCON® 260
Checking control functions
This section describes how you can check the device's control functions:
ü
Supply voltage must be present.
ü
All motor-drive units must be in the same tap position.
1.
Press
to select manual mode.
2.
Set transmission ratio for voltage transformer, current transformer and
measuring set-up.
3.
Measure actual voltage and compare with the measured value dis-
played on the device's main screen.
4.
Press
key several times to display the operating values for current,
power and phase angle and compare them with values of service instru-
ments.
5.
Control all on-load tap-changers manually with the
or
keys and
the "ED all" selection until the measured voltage (U
actual
) reaches the de-
sired voltage (U
desired
) set in the next stage.
6.
Set desired value 1 to the value you want [
7.
Set bandwidth depending on step voltage [
8.
Set delay time T1 to 20 seconds [
9.
Set control response T1 to linear [
10. Press
and select the "ED all" option to raise the on-load tap-chang-
er 1 step.
11. Press
to select auto mode.
ð
After 20 seconds, the device returns the on-load tap-changer to the
original operating position.
12. Press
to select manual mode.
13. Press
and select the "ED all" option to lower the on-load tap-chang-
er 1 step.
14. Press
to select auto mode.
ð
After 20 seconds, the device returns the on-load tap-changer to the
original operating position.
15. Press
to select manual mode.
16. Set delay time T2 to 10 seconds [
17. Activate delay time T2.
18. Press
twice and select the "ED all" option to raise the on-load tap-
changer 2 steps.
5.3.1
Содержание TAPCON 260
Страница 160: ...13 Technical data Maschinenfabrik Reinhausen 2014 160 2374092 04 EN TAPCON 260 Figure 92 Dimensions ...
Страница 167: ......