5 Commissioning
Maschinenfabrik Reinhausen 2014
42
2374092/04 EN
TAPCON® 260
Setting line drop compensation (optional)
If you need line drop compensation, you must set all important parameters
for this:
1.
Select the LDC compensation method [
2.
Set the line data for the ohmic voltage drop Ur [
3.
Set the line data for the inductive voltage drop Ux [
Setting parallel operation on several banks of transformers (optional)
If you need parallel operation, you must set all important parameters for this:
1.
Set the parallel operation method to the circulating reactive current
method [
2.
3.
Set circulating reactive current sensitivity [
4.
Set circulating reactive current blocking [
Setting control system protocol (optional)
If you need a control system protocol, you must set all important parameters
for this. More detailed information about this can be found in the control sys-
tem protocol description.
Setting tap position capture via analog input (optional)
If you want to capture the tap position via the analog input, you must set the
parameters required for this:
► Capture tap positions via analog input (input 1 or input 2) [
All parameters relevant to commissioning are entered. Continue with the
function tests.
Function tests
Before switching from manual mode to auto mode, Maschinenfabrik Rein-
hausen recommends carrying out function tests. These function tests are de-
scribed in the following sections. Note the following points for all function
tests:
▪
You must ensure that the REMOTE mode is disabled before you can
control the on-load tap-changer manually in manual mode.
▪
You can only activate the on-load tap-changer manually in manual
mode using the
and
keys.
▪
During the function test, you must set the most important parameters.
Details on the parameters listed can be found in the Functions and set-
tings [