6 Functions and settings
Maschinenfabrik Reinhausen 2014
104
2374092/04 EN
TAPCON® 260
Relative value
To set the undervoltage threshold, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Memo-
ry.
ð
V< threshold.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The undervoltage threshold is set.
Absolute value
Entries can be made either in V or kV. If you enter the absolute value in V, it
relates to the secondary transformer voltage. If you enter the absolute value
in KV, it relates to the primary voltage.
To set the undervoltage threshold, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Memo-
ry > Press
until the desired parameter is displayed.
ð
V< memory.
2.
If necessary press
to select the unit you want,
V
or
kV
.
3.
If
V
is selected, press
to highlight the decimal place.
ð
The decimal place is now highlighted and the value can be
changed.
4.
Press
to increase the value or
to reduce it.
5.
Press
.
ð
The undervoltage threshold is set.
Setting overvoltage threshold
You can use these parameters to set the overvoltage threshold as a relative
or absolute value. If the voltage exceeds the set overvoltage threshold, high-
resolution measured values are saved for as long as this situation prevails.