6 Mounting
Maschinenfabrik Reinhausen GmbH 2022
49
8595028/00 EN
TAPCON
®
250
6.2 Minimum distances
NOTICE
Damage to the device!
Insufficient circulation of ambient air can result in damage to the device due
to overheating.
► Keep the ventilation slots clear.
► Ensure sufficient distance to neighboring components.
► Only mount device in horizontal position (ventilation slots are at the top
and bottom).
To the base of the control cabinet
Minimum clearance:
Above/below: 30 mm (1.18 in)
Left/right 30 mm (1.18 in)
Depth 30 mm (1.38 in)
To the roof of the control cabinet
Between the device and other as-
semblies on offset cap rails
Table 9: Minimum clearances in the control cabinet
Figure 33: Minimum clearances
Attach the control cabinet to the transformer such that you can actuate dis-
play and control elements such as handles and push buttons at a height of
0.2…2 m above the floor space of the switchgear assembly.
For other installation types, contact Maschinenfabrik Reinhausen GmbH.
6.3 Assembly variants
6.3.1 Flush panel mounting
The device can be mounted in a control panel using tension clamps. The
recommended wall thickness is 2...5 mm.