9 Operation
Maschinenfabrik Reinhausen GmbH 2022
91
8595028/00 EN
TAPCON
®
250
Severity level
Description
Warning
Warning state
Notice
Notice state
Info
Information state
Debug
Debug state
Table 18: Severity levels
9.1.6 SCADA
The following section describes how you can configure the device for con-
nection to a control system (SCADA). You can download the data points with
the help of the export manager.
9.1.6.1 Configuring IEC 61850
If you want to use the IEC 61850 control system protocol, you must set the
following parameters. Also refer to the section Configuring the network.
1. Go to
Settings > Parameters > System > IEC 61850
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
IED name
You can use this parameter to assign the device an IED name in order for it
to be identified in the IEC 61850 network.
Device ID
You can use this parameter to assign a device ID to the device in order that
it can be identified in the IEC 61850 network.
Access point
You can use this parameter to assign a name to the access point in the IEC
61850 network.
9.1.6.1.1 Downloading an ICD file
You can download the ICD file from the device via the Import/Export Man-
ager. To do this, you have to establish an Ethernet connection between the
device and your PC.