3 IT security
Maschinenfabrik Reinhausen GmbH 2022
20
8595028/00 EN
TAPCON
®
250
Figure 2: Interfaces: CI-8520
Interface
Protocol
Port
Description
X1
TCP
102
IEC 61850
X1
TCP
502
Modbus
1)
X1
TCP
20000
DNP3
1)
X1
TCP
2404
IEC 60870-5-104
1)
X2
TCP
80
HTTP for web-based visualization
2)
X2
TCP
443
HTTPS for web-based visualization
3)
X3
TCP
80
Internal system interface (display)
2)
X3
TCP
443
Internal system interface (display)
3)
X4
TCP
80
HTTP for web-based visualization
2)
X4
TCP
443
HTTPS for web-based visualization
3)
X5
TCP
10003
Internal system interface
X5
TCP
10004
Internal system interface
Table 6: Interfaces and open ports of the CI assembly
1)
Default setting; if you have modified the port for the control system proto-
col, only the set port is open.
2)
Port is closed if you activate the device's SSL encryption.
3)
Port is opened if you activate the device's SSL encryption.