13 Technical data
Maschinenfabrik Reinhausen GmbH 2022
195
8595028/00 EN
TAPCON
®
250
Interface
Pin
Description
1
2
3
4
4
Not used
3
V1- current input
2
V1+ current output
1
Not used
Table 88: Connector X2 (group 1)
Interface
Pin
Description
1
2
3
4
4
Not used
3
V2- current input
2
V2+ current output
1
Not used
Table 89: Connector X3 (group 2)
Interface
Pin
Description
1
2
3
4
4
Not used
3
V3- current input
2
V3+ current output
1
Not used
Table 90: Connector X4 (group 3)
13.2.11 Current measurement I 3
I 3
Measurement
3-phase
Nominal current I
N
0.5...6 A
1 A / 2 A / 5 A / 6 A
Overload capability
2 x I
N
Measuring accuracy
Deviation < ±0.5% · I
N
Rated frequency
50 / 60 / 16.7 Hz
Intrinsic consumption
< 0.1 W up to I = 1 A
< 0.3 W up to I = 5 A
Table 91: I 3 assembly technical data