To activate/deactivate TDSC using parameters, proceed as follows:
1. Go to
Settings > Parameters > Control > Activate TDSC
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
TDSC Umax/Umin
You can use these parameters to set the maximum and minimum desired
value. The maximum or minimum desired value is activated when the mea-
sured active power reaches the set minimum or maximum active power.
1. Go to
Settings > Parameters > Control > TDSC Umax/Umin
.
2. Enter maximum/minimum desired value.
3. Press the
Accept
button to save the modified parameter.
TDSC U0
You can use this parameter to set the desired value which is to be used
when the measured active power is 0.
1. Go to
Settings > Parameters > Control > TDSC U0
.
2. Enter desired value at active power 0.
3. Press the
Accept
button to save the modified parameter.
TDSC Pmax/Pmin
You can use these parameters to set the maximum and minimum active
power value at which the maximum and minimum active power-dependent
desired value is to be used for regulation.
1. Go to
Settings > Parameters > Control > TDSC Pmax/Pmin
.
2. Enter active power for maximum/minimum desired value.
3. Press the
Accept
button to save the modified parameter.
Bandwidth
You can use this parameter to set the maximum permissible deviation of the
measured voltage U
actual
from the desired value U
desired
.
In order to set the correct value, the transformer step voltage and nominal
voltage must be known. Note that a large bandwidth will result in a large
control deviation.