5 Mounting
Maschinenfabrik Reinhausen 2014
32
222/08 EN
TAPCON® 240
Mounting
This chapter describes how to correctly mount and connect the device. Note
the connection diagrams provided.
WARNING
Electric shock
Risk of fatal injury due to electrical voltage.
► De-energize the device and system peripherals and lock them to pre-
vent them from being switched back on.
► Do so by short-circuiting the current transformer; do not idle the current
transformer.
NOTICE
Electrostatic discharge
Damage to the device due to electrostatic discharge.
► Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
Preparation
The following tools are needed for mounting:
▪
Screwdriver for the fixing bolts (M6)
▪
Small screwdriver for connecting the signal lines and supply lines
Depending on installation site and mounting variant, you may need addition-
al tools and corresponding attachment material (screws, nuts, washers)
which are not included in the scope of supply.
Mounting device
Depending on your order, you can mount the device in one of the following
variants:
▪
19" frame (in accordance with DIN 41494 Part 5)
▪
19" flush control panel frame
▪
½-19" mounting frame for wall mounting
Below you will find a description of how to mount the device in a 19" frame.
For control panel installation or wall mounting, note the technical files sup-
plied.
To mount the device in a 19" frame, proceed as follows:
1.
Place cage nuts in the desired locations on the 19" frame, noting the
device dimensions [
5
5.1
5.2