14 Appendix
118
BA6820378-03 EN
14.1 Modbus RTU
Status information
Function code "02" for reading the information
No.
Value
Designation
DB100/200/200D DB200G
0
ON/
OFF
Error present
Yes
Yes
1
ON/
OFF
Left SiO2 heating error
Yes
Yes
2
ON/
OFF
Right SiO2 heating error
DB200D only
Yes
3
ON/
OFF
Voltage supply error
Yes
Yes
4
ON/
OFF
Left sensor error
Yes
Yes
5
ON/
OFF
Right sensor error
DB200D only
Yes
6
ON/
OFF
Right gamma error
No
Yes
7
ON/
OFF
Left gamma error
No
Yes
8
ON/
OFF
RTC battery low
Yes
Yes
9
ON/
OFF
Analog output 1 open
Yes
Yes
10
ON/
OFF
Analog output 2 open
Yes
Yes
11
ON/
OFF
Alpha controller info
Yes
No
12
ON/
OFF
Beta controller info
Yes
No
13
ON/
OFF
Info two cylinders
DB200D
Yes
14
ON/
OFF
Gamma controller info
No
Yes
15
ON/
OFF
Left cylinder closed
No
Yes
Содержание MESSKO MTRAB
Страница 1: ...Dehydrating breather MESSKO MTRAB Operating instructions BA6820378 03 EN Version 2 5 ...
Страница 19: ...3 Product description 19 BA6820378 03 EN 3 2 Design versions Figure 1 Design ...
Страница 82: ...8 Operation 82 BA6820378 03 EN Figure 62 Ball valve 1 Switch 2 Ball valve 3 Display 4 Ball valve control cable ...
Страница 84: ...9 Error messages and troubleshooting 84 BA6820378 03 EN Figure 63 LEDs 1 Green LED 2 Yellow LED 3 Red LED ...
Страница 102: ...11 Disposal 102 BA6820378 03 EN Observe the national disposal regulations in the country of use ...
Страница 114: ......
Страница 121: ......
Страница 122: ......
Страница 123: ......