5 Mounting
38
BA5789879-01 EN
6. First tighten the inner cable screw connection hand-tight, and then the
outer cable screw connection, and ensure that the cables and braided
leads remain loose and without tension, and that they are not twisted.
7. Tighten all cable screw connections with max. torque = 5.0 Nm.
8. Close the cover of the micro-switch housing using the 4 cover bolts with a
max. torque = 2.0 Nm.
9. Replace the protective cover.
5.3.2 Connecting the cable to the terminal box
To connect the device to the terminal box, proceed as follows:
1. Undo the 4 screws in the cover of the terminal box using a crosshead
screwdriver.
2. Remove the sheathing of the cable to be connected, strip off approx. 7
mm of insulation from the braided leads and cap off with ferrules.
3. Open the cable screw connection M25x1.5 (for cables Ø 13–20 mm)
(wrench size 32) and pull the cable through.
Figure 16: Connection diagram for terminal box
1 Standard protective cover
2 OD protective cover
4.
NOTICE!
Do not kink the braided leads! Connect the signal lines and pro-
tective conductor to the labeled terminal strip in loose arcs in accordance
with the connection diagram.