5 Mounting
31
BA5789879-01 EN
Mounting the device
1. Place the mounting seal ring (delivered as an option) under the device,
see Dimensions with OD protective cover [
2. Mount the device onto the counter flange on the transformer / on-load tap-
changer by inserting 6 screws M12 or 1/2" (not supplied) through the drill
holes in the device flange.
Figure 8: Mounting the device
1 Mounting seal ring Ø 200 x Ø
178.5 x 4.25 mm [Ø 7.87" x Ø7.03"
x 0.17"]
2 6 screws M12 or 1/2"
3 Through bar of the device flange
Closing the device
After mounting, close the device as follows:
1. If the device is equipped with micro-switches for remote transmission of
the signals, first connect these micro-switches, see Electrically connecting
the pressure relief device [