BA 3527161/02 EN
13
7 Technical data
Dimensions
Refer to chap. 8.1
Materials
Housing:
Die casted aluminium,
polyester powder coated,
RAL 7033
Viewing glass:
Laminated safety glass
(standard); UV stabilized
polycarbonate (optional)
Capillary tube:
Square flange 4 holes;
G3/4“; G1“; 7/8“-14UNF;
other thread joints on
request
Cable glands:
Up to 3 x M20 x 1.5
and 1 x M16 for analogue
output
Specifications
Measuring ranges:
0...150 °C or
-20...130 °C or
0...160 °C or
-40...160 °C;
other ranges on request
Indication accuracy:
± 3 °C (30-150 °C)
(optional:
± 2 °C or 1.5 °C)
Place of installation:
Indoors and outdoors,
tropical and arctic climate
Ambient temperature:
-40 ... +70 °C
(optional: polar execution
down to -60 °C)
Insulation voltage:
2.5 kV 50 Hz 1 min
Protection class:
IP 55 in accordance with
IEC 60 529;
(optional: IP 65)
Analog output:
4-20 mA; 4-20 mA and
5 V DC; 5 V DC; Pt100
Weight:
Approx. 4 kg
Microswitches
Number:
2, 3, 4 or 5
Switch rating:
Standard SPDT 250 V AC /
15 A;
(optional:
MBO SPDT 250 V AC/10 A
or 250 V DC / 5 A,
DPDT or gold plated SPDT)
Switch hysteresis:
12 °C ± 2 °C; others on
request
7