9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
96
4453918/14 EN
ETOS
®
TD
Note that all SCADA clients communicate with the device on an equal basis,
because the device does not prioritize commands. If you transmit com-
mands from several SCADA clients to the device at the same time, the de-
vice will execute the last transmitted command.
9.7.5 Configuring Modbus (optional)
If you want to use the Modbus control system protocol, you must set the cor-
responding parameters depending on the Modbus type selected. Also refer
to the section Configuring the network [
Section 9.3, Page 79] if you want
to use Modbus TCP.
Settings
Parameters
Modbus
Name
Value
Modbus type
RTU
Modbus address
1
TCP port
502
Maximum TCP connections
10
TCP Keepalive
Off
Serial interface
RS232
Baud rate
9600
Number of databits
8
Parity
Even
Number of stop bits
1
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
31.01.2020 13:05
Figure 68: Modbus
1. Go to
Settings > Parameters > System > Modbus
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Modbus type
You can use this parameter to set the Modbus type. You can select the fol-
lowing options:
▪ RTU
▪ TCP
▪ ASCII
Modbus address
You can use this parameter to set the Modbus address.
TCP port
You can use this parameter to set the TCP port.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......