9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
231
4453918/14 EN
ETOS
®
TD
Settings
Parameters
OLTC PreCheck
Name
Value
Activate OLTC precheck
Off
OLTC oil level >>
95 %
OLTC oil level <<
65 %
OLTC oil temperature >>
110°C
I>> relative/absolute
Relative
I>> [A]
1 kA
I>> [%]
110 %
I>> hysteresis
0 kA
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
05.02.2020 10:09
Figure 166: Configuring OLTC PreCheck
To configure OLTC PreCheck, proceed as follows:
1. Go to
Settings > Parameters > OLTC PreCheck
.
2. Select the parameter you want.
3. Set parameter.
4. Press the
Accept
button to save the modified parameter.
9.25.7 Information about the on-load tap-changer
Under "OLTC" you can display information about the on-load tap-changer:
▪ Current tap position
▪ Total tap-change operations (operations counter)
Figure 167: OLTC
► Go to
Information > On-load tap-changer > OLTC
.