9.22.11 Monitoring the gas volume of the Buchholz relay (transformer)
When you record the gas volume of the Buchholz relay of the transformer,
you can set 2 limit values for the gas volume. If the measured gas volume is
greater than the limit value > or >>, the device triggers an event message.
Settings
Parameters
Buchholz relay
>
>>
Transformer gas volume
0.3 l
0.4 l
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 143: Limit values for the gas volume of the Buchholz relay of the transformer
1. Go to
Settings > Parameters > Active part > Buchholz relay
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
9.22.12 Monitoring the oil pressure (transformer)
When you record the oil pressure of the transformer, you can use the pres-
sure relief device (PRD) to set 2 limit values for the gas volume. If the mea-
sured oil pressure is greater than the limit value > or >>, the device triggers
an event message.
Settings
Parameters
Pressure...ice
>
>>
Transformer oil press.
15 kPa
20 kPa
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 144: Limit values for the oil pressure of the transformer
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......