9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
140
4453918/14 EN
ETOS
®
TD
9.15 Voltage regulation
All of the parameters required for voltage regulation are described in this
section.
Settings
Parameters
Voltage re...ion
Name
Value
Desired value 1
100 V
Desired value 2
100 V
Desired value 3
100 V
Selecting a desired value
Desired value 1
Bandwidth
1.0 %
Delay time T1
40 s
Time response T1
Linear
Activate delay time T2
Off
Delay time T2
10 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 104: Voltage regulation (example)
1. Go to
Settings > Parameters > On-load tap-changer regulator > Volt-
age regulation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
9.15.1 Setting the desired value
In accordance with the order, the device is equipped with one of the follow-
ing variants for setting the desired value:
9.15.1.1 Desired value 1
1. Go to
Settings > Parameters > Grid > Control > Desired value
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
9.15.1.2 Desired value 1...3
You can set 3 different desired values. The device always uses one of the
set desired values for control. You can define the desired value used for
control by means of the "Select desired value" parameter or with the digital
inputs.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......