7 Operation
Maschinenfabrik Reinhausen GmbH 2019
94
5163667/06 EN
ETOS
®
IM
4. Enter the visualization's IP address (e.g.
http://192.0.1.230
, if SSL
encryption is active enter
https://192.0.1.230
) on the PC in the
browser.
ð
The visualization is accessed.
7.2 General
You can set general parameters in this menu item.
Also refer to
2
7.2.1 Configuring visualization
You can use the following parameters to configure the interface for the visu-
alization. The following parameters are available:
▪ IP address
▪ Subnet mask
▪ Gateway address
▪ SSL encryption
IP address, subnet mask and gateway address
You can use these parameters to undertake the network configuration for
the visualization. These settings apply to access via the ETH2.2 interface on
the CPU module.
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connec-
tion.
1. Go to
Settings > Parameters > General > IP address
,
Subnet mask
or
Gateway
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
Activating SSL/TLS encryption
You can use this parameter to set whether access to the visualization should
take place over an SSL-encrypted connection.
To activate SSL encryption, proceed as follows:
1. Go to
Settings > Parameters > General > SSL/TLS encryption
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.