5163667/06 EN
ETOS
®
IM
5.6.1 Cable recommendation
Please note the following Maschinenfabrik Reinhausen recommendation
when wiring the device.
Excessive line capacitance can prevent the relay contacts from breaking the
contact current. In control circuits operated with alternating current, take into
account the effect of the line capacitance of long control cables on the func-
tion of the relay contacts.
If you want to route Ethernet connections from a control cabinet or building,
we recommend the use of fiber-optic cables (in accordance with the IEC
61850-90-4 recommendation).
Cable
Assembly
Cable type
Conductor cross-sec-
tion
Max. length
Power supply (external)
OT1205, G1
PULS
QS3.241
Unshielded
1.5 mm²
-
Power supply (internal, 24
VDC)
CPU, DIO,
AIO, MC, SW
Unshielded
1.5 mm²
-
Voltage measurement
UI 1, UI 1-1, UI
3
Shielded
2.5 mm²
-
Current measurement
UI 1, UI 1-1, UI
3
Unshielded
4 mm²
-
Signal inputs
DIO 28-15,
DIO 42-20
Shielded
1.5 mm
2
400 m (<25 Ω/km)
Signal outputs*
DIO 28-15,
DIO 42-20
Shielded
1.5 mm
2
-
Signal inputs
AIO 2, AIO 4,
AIO 8
Shielded
1 mm
2
400 m (<25 Ω/km)
Signal outputs
AIO 2, AIO 4,
AIO 8
Shielded
1 mm
2
-
RS232, SUB-D
CPU I, CPU II
Shielded
0.25 mm
2
25 m
RS485; SUB-D
CPU I, CPU II
Shielded
0.25 mm
2
140 m
CAN bus
CPU I
Shielded
0.75 mm²
2,000 m (total CAN bus)
Ethernet RJ45
CPU I
Min. CAT5, shielded
S/FTP
-
100 m
Ethernet FO
MC2-2, SW3-3 Duplex LC
Multimode, OM3,
1310 nm
-
2000 m
Table 10: Recommendation for connection cables
*) Observe line capacitance, see note above.