![MR ETOS IM Скачать руководство пользователя страница 252](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393252.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
252
5163667/06 EN
ETOS
®
IM
To call up the overload table, proceed as follows:
1. Go to
Information > Overload table
.
2. If necessary, select the
Update
button to update the view.
Overload diagram
In this menu, you can display the calculated values graphically. For the se-
lected overload period, the diagram shows the permissible load factor K and
the forecast progression of the temperatures (hot-spot, top-oil) as well as the
associated limit values. Furthermore, the diagram shows the progression of
the forecast loss-of-life and the ambient temperature at the time of the calcu-
lation.
If you call up the visualization via a PC and your user role is either "Diagnos-
tics", "Parameter Configurator" or "Administrator", you can export the over-
load diagram data values as a csv file.
Figure 192: Overload diagram
To call up the overload diagram, proceed as follows:
1. Go to
Information > Overload diagram
.
2. Select the desired
Overload period
.
3. If necessary, select the
Update
button to update the view.
4. If required, select the
button to export the overload diagram data.
7.22 Event management
The device is equipped with event management, which allows you to detect
various device operating statuses and to adapt the behavior of the device.
An overview of all possible events is given in the Event messages chapter.